Table 95 — Gas Heating Service Analysis
Table 96 — Electric Heat Service Analysis
PROBLEM CAUSE
REMEDY
Burners Will Not Ignite.
Active alarm.
Check active alarms using
Comfort
Link™ scrolling
marquee.
No power to unit.
Check power supply, fuses, wiring, and circuit breakers.
No power to IGC (Integrated Gas Control).
Check fuses and plugs.
Heaters off due to time guard to prevent short
cycling.
Check using
Comfort
Link scrolling marquee.
Control calling for Cooling.
Check using
Comfort
Link scrolling marquee.
No gas at main burners.
Check gas line for air and purge as necessary. After purg-
ing gas line of air, allow gas to dissipate for at least 5 min-
utes before attempting to re-light unit.
Water in gas line.
Drain water and install drip.
Inadequate Heating.
Dirty air filters.
Replace air filters.
Gas input too low.
Check gas pressure at manifold. Refer to gas valve adjust-
ment in Installation, Start-up, and Service Manual.
Control calling for W1only (low heat).
Allow time for W2 to energize.
Unit undersized for load.
Decrease load.
Restricted airflow.
Remove restriction.
Too much outdoor air.
Check economizer position and configuration. Adjust mini-
mum position using
Comfort
Link scrolling marquee
.
Limit switch cycles main burners.
Check rotation of blower, thermostat heat anticipator set-
tings, and temperature rise of unit. Adjust as needed.
Poor Flame Characteristics.
Incomplete combustion (lack of combustion air)
results in: Aldehyde odors, CO, sooting flame, or
floating flame.
Check all screws around flue outlets and burner compart-
ment. Tighten as necessary.
Cracked heat exchanger, replace.
Unit is over-fired, reduce input. Adjust gas line or manifold
pressure.
Check vent for restriction. Clean as necessary.
Check orifice to burner alignment.
Burners Will Not Turn Off.
Unit is in minimum on-time.
Check using
Comfort
Link scrolling marquee.
Unit running in Service Test mode.
Check using
Comfort
Link scrolling marquee.
PROBLEM CAUSE
REMEDY
No Heat.
Power failure.
Call power company.
Fuse blown or circuit breaker tripped.
Replace fuse or reset circuit breaker.
Thermostat occupancy schedule set point not call-
ing for Heating.
Check using
Comfort
Link scrolling marquee.
No 24 vac at primary contactor.
Check transformer and circuit breaker.
No power (high voltage) to L2 of primary contactor. Check safety switches “one-shot” backup and auto limit.
Bad electrical elements.
Power off unit and remove high voltage wires. Check resis-
tance of heater, replace if open.
Содержание WEATHERMAKER 48/50AJ
Страница 103: ...103 Fig 15 Typical Main Control Box Wiring Schematic 48 50AJ AK AW AY Units cont a48 8355 ...
Страница 104: ...104 Fig 16 Typical Main Control Box Wiring Schematic 48 50A2 A3 A4 A5 Units a48 8355 ...
Страница 105: ...105 TO NEXT PAGE Fig 17 Typical Auxiliary Control Box Wiring Schematic A48 7294 ...
Страница 106: ...106 Fig 17 Typical Auxiliary Control Box Wiring Schematic cont a48 8356 ...
Страница 107: ...107 Fig 18 Typical 2 Stage Gas Heat Wiring Schematic Size 051 and 060 Units Shown a48 8357 ...
Страница 108: ...108 TO NEXT PAGE Fig 19 Typical Staged Gas Heat Wiring Schematic Size 051 and 060 Units Shown A48 7296 ...
Страница 109: ...109 Fig 19 Typical Staged Gas Heat Wiring Schematic Size 051 and 060 Units Shown cont A48 8358 ...
Страница 110: ...110 Fig 20 Typical Electric Heat Control Schematic 50 Series Size 051 and 060 Units Shown a50 8228 ...
Страница 111: ...111 TO NEXT PAGE Fig 21 Typical Power Schematic 48 50AJ AK AW AY051 and 060 Units Shown A48 7298 ...
Страница 112: ...112 FROM PREVIOUS PAGE Fig 21 Typical Power Schematic 48 50AJ AK AW AY051 and 060 Units Shown cont a48 8360 ...
Страница 113: ...113 Fig 22 Typical Power Schematic 48 50A2 A3 A4 A5060 Unit Shown ...
Страница 114: ...114 SW1 SW2 OR DEHUMIDIFY SWITCH Fig 23 Typical Controls Option Wiring Schematic a48 8361 ...
Страница 115: ...115 Fig 24 Typical Small Chassis Component Location Size 020 035 Units a48 8362 ...
Страница 116: ...116 Fig 25 Typical Large Chassis Component Locations Size 036 060 Units A48 7302 ...
Страница 169: ...169 APPENDIX C VFD INFORMATION cont Fig F Internal Enclosure Fan Replacement A48 7716 ...