176
APPENDIX E — UPC OPEN CONTROLLER (cont)
NETWORK POINTS LIST
See legend on page 182.
BACNET
OBJECT ID
POINT NAME
READ
ONLY
UNITS
DEFAULT
VALUE
RANGE
BACNET
OBJECT NAME
UNIT
POINT
AV:9
Active Demand Limit
W
%
n/a
0-100
dem_lim_1
DEM_LIM
AV:10
Air Temp Lvg Supply Fan
R
°F
n/a
n/a
sat_1
SAT
AV:11
CEM AN1 4-20 ma J5,1-2
W
mA
n/a
0-20
cem4201_1
CEM4201
AV:12
CEM AN1 10K temp J5,1-2
W
°F
n/a
-40-240
cem10k1_1
CEM10K1
AV:13
CEM AN2 4-20 ma J5,3-4
W
mA
n/a
0-20
cem4202_1
CEM4202
AV:14
CEM AN2 10K temp J5,3-4
W
°F
n/a
-40-240
cem10k2_1
CEM10K2
AV:15
Temper Supply Air Setpt
W
°F
n/a
0-100
sasptemp_1
SASPTEMP
AV:16
BP PID Evaluation Time Level
W
min
1
0-10
bpperiod_1
BPPERIOD
AV:17
BP Setpoint Offset
W
in H2O
0.05
0-0.5
bpso_1
BPSO
AV:18
BP Threshold Adjustment
W
n/a
1
0.1-10
bpz_gain_1
BPZ_GAIN
AV:22
Capacity Load Factor
R
%
n/a
n/a
smz_1
SMZ
AV:23
Capacity Threshold Adj
W
n/a
1
0-10
z_gain_1
Z_GAIN
AV:24
Compressor A1 Run Hours
R
hr
n/a
n/a
hr_a1_1
HR_A1
AV:25
Compressor A1 Starts
R
n/a
n/a
n/a
cy_a1_1
CY_A1
AV:26
Compressor A1 Strikes
R
n/a
n/a
n/a
cmpa1str_1
CMPA1STR
AV:27
Compressor A1 Timeguard
R
n/a
n/a
n/a
cmpa1_tg_1
CMPA1_TG
AV:28
Compressor A2 Run Hours
R
hr
n/a
n/a
hr_a2_1
HR_A2
AV:29
Compressor A2 Starts
R
n/a
n/a
n/a
cy_a2_1
CY_A2
AV:30
Compressor A2 Strikes
R
n/a
n/a
n/a
cmpa2str_1
CMPA2STR
AV:31
Compressor A2 Timeguard
R
n/a
n/a
n/a
cmpa2_tg_1
CMPA2_TG
AV:32
Compressor B1 Run Hours
R
hr
n/a
n/a
hr_b1_1
HR_B1
AV:33
Compressor B1 Starts
R
n/a
n/a
n/a
cy_b1_1
CY_B1
AV:34
Compressor B1 Strikes
R
n/a
n/a
n/a
cmpb1str_1
CMPB1STR
AV:35
Compressor B1 Timeguard
R
n/a
n/a
n/a
cmpb1_tg_1
CMPB1_TG
AV:36
Compressor B2 Run Hours
R
hr
n/a
n/a
hr_b2_1
HR_B2
AV:37
Compressor B2 Starts
R
n/a
n/a
n/a
cy_b2_1
CY_B2
AV:38
Compressor B2 Strikes
R
n/a
n/a
n/a
cmpb2str_1
CMPB2STR
AV:39
Compressor B2 Timeguard
R
n/a
n/a
n/a
cmpb2_tg_1
CMPB2_TG
AV:40
Compressor Lockout Temp
W
°F
40
-20-55
oatlcomp_1
OATLCOMP
AV:41
Cool Trend Demand Level
W
°^F
0.1
0.1-5
ctrendlv_1
CTRENDLV
AV:42
Cool Trend Time (secs)
W
sec
120
30-600
ctrendtm_1
CTRENDTM
AV:43
Ctl.Temp RAT,SPT or ZONE
R
°F
n/a
n/a
ctrltemp_1
CTRLTEMP
AV:44
Current Running Capacity
R
%
n/a
n/a
htsg_cap_1
HTSG_CAP
AV:45
DAQ PPM Fan Off Setpoint
W
n/a
200
0-2000
daqfnoff_1
DAQFNOFF
AV:46
DAQ PPM Fan On Setpoint
W
n/a
400
0-2000
daqfnon_1
DAQFNON
AV:49
Dehumidify Cool Setpoint
W
°F
45
40-55
dhcoolsp_1
DHCOOLSP
AV:50
Dehumidify RH Setpoint
W
%
55
10-90
dhrelhsp_1
DHRELHSP
AV:52
Demand Limit Select
W
n/a
0
0-3
dmd_ctrl_1
DMD_CTRL
AV:53
Demand Limit Sw.1 Setpt.
W
%
80
0-100
dlswsp1_1
DLSWSP1
AV:54
Demand Limit Sw.2 Setpt.
W
%
50
0-100
dlswsp2_1
DLSWSP2
AV:56
Diff.Air Quality in PPM
R
n/a
n/a
n/a
daq_1
DAQ
AV:58
Diff. AQ Responsiveness
W
n/a
0
-5-5
iaqreact_1
IAQREACT
AV:59
Dmd Level(-) Low Cool OFF
W
°^F
1
0.5-2
dmdlcoff_1
DMDLCOFF
AV:60
Dmd Level(-) Low Heat OFF
W
°^F
1
0.5-2
dmdlhoff_1
DMDLHOFF
Содержание WEATHERMAKER 48/50AJ
Страница 103: ...103 Fig 15 Typical Main Control Box Wiring Schematic 48 50AJ AK AW AY Units cont a48 8355 ...
Страница 104: ...104 Fig 16 Typical Main Control Box Wiring Schematic 48 50A2 A3 A4 A5 Units a48 8355 ...
Страница 105: ...105 TO NEXT PAGE Fig 17 Typical Auxiliary Control Box Wiring Schematic A48 7294 ...
Страница 106: ...106 Fig 17 Typical Auxiliary Control Box Wiring Schematic cont a48 8356 ...
Страница 107: ...107 Fig 18 Typical 2 Stage Gas Heat Wiring Schematic Size 051 and 060 Units Shown a48 8357 ...
Страница 108: ...108 TO NEXT PAGE Fig 19 Typical Staged Gas Heat Wiring Schematic Size 051 and 060 Units Shown A48 7296 ...
Страница 109: ...109 Fig 19 Typical Staged Gas Heat Wiring Schematic Size 051 and 060 Units Shown cont A48 8358 ...
Страница 110: ...110 Fig 20 Typical Electric Heat Control Schematic 50 Series Size 051 and 060 Units Shown a50 8228 ...
Страница 111: ...111 TO NEXT PAGE Fig 21 Typical Power Schematic 48 50AJ AK AW AY051 and 060 Units Shown A48 7298 ...
Страница 112: ...112 FROM PREVIOUS PAGE Fig 21 Typical Power Schematic 48 50AJ AK AW AY051 and 060 Units Shown cont a48 8360 ...
Страница 113: ...113 Fig 22 Typical Power Schematic 48 50A2 A3 A4 A5060 Unit Shown ...
Страница 114: ...114 SW1 SW2 OR DEHUMIDIFY SWITCH Fig 23 Typical Controls Option Wiring Schematic a48 8361 ...
Страница 115: ...115 Fig 24 Typical Small Chassis Component Location Size 020 035 Units a48 8362 ...
Страница 116: ...116 Fig 25 Typical Large Chassis Component Locations Size 036 060 Units A48 7302 ...
Страница 169: ...169 APPENDIX C VFD INFORMATION cont Fig F Internal Enclosure Fan Replacement A48 7716 ...