157
APPENDIX B — CCN TABLES (cont)
MAINTENANCE DISPLAY TABLES (cont)
TABLE
DISPLAY NAME
RANGE
UNITS
POINT NAME
WRITE STATUS
ECON_MIN
Econo Damper Command Pos
%
ECONOCMD
forcible
Econo Damper Current Pos
%
ECONOPOS
Econo Current Min. Pos.
%
ECMINPOS
Diff.Air Quality in PPM
DAQ
Econo Position Override
ECOORIDE
forcible
IAQ Min.Pos.Override
%
IAQMINOV
forcible
Econ Remote 10K Pot Val.
ECON_POT
forcible
IAQ - PPM Return CO2
IAQ
forcible
OAQ - PPM Return CO2
OAQ
forcible
IAQ - Discrete Input
IAQIN
forcible
IAQ Demand Vent Min.Pos.
%
IAQMINP
config
Economizer Min.Position
%
ECONOMIN
config
IAQ Analog Sensor Config
IAQANCFG
config
IAQ 4-20 ma Fan Config
IAQANFAN
config
IAQ Discrete Input Confg
IAQINCFG
config
IAQ Disc.In. Fan Config
IAQINFAN
config
IAQ Econo Override Pos.
%
IAQOVPOS
config
Diff.Air Quality LoLimit
DAQ_LOW
config
Diff.Air Quality HiLimit
DAQ_HIGH
config
DAQ PPM Fan Off Setpoint
DAQFNOFF
config
DAQ PPM Fan On Setpoint
DAQFNON
config
Diff. AQ Responsiveness
IAQREACT
config
IAQ Low Reference
IAQREFL
config
IAQ High Reference
IAQREFH
config
OAQ Lockout Value
OAQLOCK
config
OAQ 4-20ma Sensor Config
ma
OAQANCFG
config
IAQ milliamps
ma
IAQ_MA
OAQ milliamps
OAQ_MA
EC_DIAG
Economizer Active ?
Yes/No
ECACTIVE
Conditions which prevent
economizer being active:
Econ Act. Unavailable?
Yes/No
ECONUNAV
Remote Econ. Disabled ?
Yes/No
ECONDISA
DBC - OAT lockout?
Yes/No
DBC_STAT
DEW - OA Dewpt. lockout?
Yes/No
DEW_STAT
DDBC- OAT > RAT lockout?
Yes/No
DDBCSTAT
OAEC- OA Enth Lockout?
Yes/No
OAECSTAT
DEC - Diff.Enth.Lockout?
Yes/No
DEC_STAT
EDT Sensor Bad ?
Yes/No
EDT_STAT
OAT Sensor Bad ?
Yes/No
OAT_STAT
Economizer forced ?
Yes/No
ECONFORC
Supply Fan not on 30s ?
Yes/No
SFONSTAT
Cool Mode not in effect?
Yes/No
COOL_OFF
OAQ lockout in effect ?
Yes/No
OAQLOCKD
Econ recovery hold off?
Yes/No
ECONHELD
Outside Air Temperature
dF
OAT
forcible
OutsideAir DewPoint Temp
dF
OADEWTMP
Outside Air Rel.Humidity
%
OARH
forcible
Outdoor Air Enthalpy
OAE
Return Air Temperature
dF
RAT
forcible
Return Air Rel.Humidity
%
RARH
forcible
Return Air Enthalpy
RAE
High OAT Lockout Temp
dF
OAT_LOCK
config
Econ ChangeOver Select
ECON_SEL
config
OA Enthalpy ChgOvr Selct
OAEC_SEL
config
Outdr.Enth Compare Value
OAEN_CFG
config
OA Dewpoint Temp Limit
dF
OADEWCFG
config
Supply Fan State
SFAN
Economizer Act.Cmd.Pos.
%
ECONOCMD
forcible
Economizer Act.Curr.Pos.
%
ECONOPOS
Evaporator Discharge Tmp
dF
EDT
Economizer Control Point
dF
ECONCPNT
EDT Trend in degF/minute
^F
EDTTREND
Economizer Prop.Gain
EC_PGAIN
config
Economizer Range Adjust
^F
EC_RANGE
config
Economizer Speed Adjust
EC_SPEED
config
Economizer Deadband
^F
EC_DBAND
config
Economizer Timer
sec
ERATETMR
config
Содержание WEATHERMAKER 48/50AJ
Страница 103: ...103 Fig 15 Typical Main Control Box Wiring Schematic 48 50AJ AK AW AY Units cont a48 8355 ...
Страница 104: ...104 Fig 16 Typical Main Control Box Wiring Schematic 48 50A2 A3 A4 A5 Units a48 8355 ...
Страница 105: ...105 TO NEXT PAGE Fig 17 Typical Auxiliary Control Box Wiring Schematic A48 7294 ...
Страница 106: ...106 Fig 17 Typical Auxiliary Control Box Wiring Schematic cont a48 8356 ...
Страница 107: ...107 Fig 18 Typical 2 Stage Gas Heat Wiring Schematic Size 051 and 060 Units Shown a48 8357 ...
Страница 108: ...108 TO NEXT PAGE Fig 19 Typical Staged Gas Heat Wiring Schematic Size 051 and 060 Units Shown A48 7296 ...
Страница 109: ...109 Fig 19 Typical Staged Gas Heat Wiring Schematic Size 051 and 060 Units Shown cont A48 8358 ...
Страница 110: ...110 Fig 20 Typical Electric Heat Control Schematic 50 Series Size 051 and 060 Units Shown a50 8228 ...
Страница 111: ...111 TO NEXT PAGE Fig 21 Typical Power Schematic 48 50AJ AK AW AY051 and 060 Units Shown A48 7298 ...
Страница 112: ...112 FROM PREVIOUS PAGE Fig 21 Typical Power Schematic 48 50AJ AK AW AY051 and 060 Units Shown cont a48 8360 ...
Страница 113: ...113 Fig 22 Typical Power Schematic 48 50A2 A3 A4 A5060 Unit Shown ...
Страница 114: ...114 SW1 SW2 OR DEHUMIDIFY SWITCH Fig 23 Typical Controls Option Wiring Schematic a48 8361 ...
Страница 115: ...115 Fig 24 Typical Small Chassis Component Location Size 020 035 Units a48 8362 ...
Страница 116: ...116 Fig 25 Typical Large Chassis Component Locations Size 036 060 Units A48 7302 ...
Страница 169: ...169 APPENDIX C VFD INFORMATION cont Fig F Internal Enclosure Fan Replacement A48 7716 ...