75
Table 89 — Switch Logic Configuration
Table 90 — Display Configuration
Table 91 — Remote Switch Configuration
Remote Switch Logic Configuration
(
Configuration
SW.LG
RMI.L
) — The control allows for the configuration
of a normally open/closed status of the remote input switch via
RMI.L
. If this variable is configured OPEN, then when the
switch is open, the remote input switch perceives the logic state
as OFF. Correspondingly, if
RMI.L
is set to CLOSED, the re-
mote input switch will perceive a closed switch as meaning
OFF. See Table 92.
Hot Gas Bypass —
Hot gas bypass is an active part of
the A-Series
Comfort
Link™ capacity staging and minimum
evaporator load protection functions. It is controlled though the
Minimum Load Valve function.
The hot gas bypass option consists of a solenoid valve with
a fixed orifice sized to provide a nominal 3-ton evaporator load
bypass. A hot gas refrigerant line routes the bypassed hot gas
from Circuit A’s discharge line to Circuit A’s evaporator
distributor. When the unit control calls for hot gas bypass, the
hot gas enters the evaporator coil and adds refrigeration load
to the compressor circuit to reduce the cooling effect from
Circuit A.
The hot gas bypass system is a factory-installed option
installed on Circuit A only. This function is enabled at
Config-
uration
COOL
MLV
. When this function is enabled, an
additional stage of cooling capacity is provided by the unit
control staging sequences (see Tables 52, 54, 58, and 60).
Space Temperature Offset —
Space temperature off-
set corresponds to a slider on a T56 sensor that allows the occu-
pant to adjust the space temperature by a configured range
during an occupied period. This sensor is only applicable to
units that are configured as either 2-Stage SPT or Multi-Stage
SPT control (
Configuration
UNIT
C.TYP
= 5 or 6).
Space Temperature Offset Sensor
(
Configuration
UNIT
SENS
SP.O.S
) — This configuration disables the reading
of the offset slider.
Space Temperature Offset Range
(
Configuration
UNIT
SENS
SP.O.R
) — This configuration establishes
the range, in degrees F, that the T56 slider can affect
SPTO
when adjusting the slider from the far left (
-
SP.O.R
) to the far
right (+
SP.O.R
). The default is 5° F.
Space Temperature Offset Value
(
Temperatures
AIR.T
SPTO
) — The Space Temperature Offset Value is the read-
ing of the slider potentiometer in the T56 that is resolved to
delta degrees based on
SP.O.R
.
TIME CLOCK CONFIGURATION
This section describes each Time Clock menu item. Not
every point will need to be configured for every unit. Refer to
the Controls Quick Start section for more information on what
set points need to be configured for different applications. The
Time Clock menu items are discussed in the same order that
they are displayed in the Time Clock table. The Time Clock
table is shown in Table 93.
Hour and Minute (
HH.MM
) —
The hour and minute
of the time clock are displayed in 24-hour, military time. Time
can be adjusted manually by the user.
When connected to the CCN, the unit can be configured to
transmit time over the network or receive time from a network
device. All devices on the CCN should use the same time. Only
one device on the CCN should broadcast time or problems will
occur.
Month of Year (
MNTH
) —
This variable is the current
month of the calendar year.
Day of Month (
DOM
) —
This variable is the current
day (1 to 31) of the month.
Day of Week (
DAY
) —
This variable is the current day
of the week (Monday = 1 through Sunday = 7).
Year (
YEAR
) —
This variable is the current year (for ex-
ample, 2005).
Local Time Schedule (
SCH.L
) —
This submenu is
used to program the time schedules. There are 8 periods
(
PER.1
through
PER.8
). Each time period can be used to set
up a local schedule for the unit.
ITEM
EXPANSION
RANGE
CCN POINT
DEFAULT
SW.LG
SWITCH LOGIC: NO / NC
FTS.L
Filter Status Inpt-Clean
Open/Close
FLTSLOGC
Open
IGC.L
IGC Feedback - Off
Open/Close
GASFANLG
Open
RMI.L
RemSw Off-Unoc-Strt-NoOv
Open/Close
RMTINLOG
Open
ECS.L
Economizer Switch - No
Open/Close
ECOSWLOG
Open
SFS.L
Fan Status Sw. - Off
Open/Close
SFSLOGIC
Open
DL1.L
Dmd.Lmt.Sw.1 - Off
Open/Close
DMD_SW1L
Open
DL2.L
Dmd.Lmt.2 Dehumid - Off
Open/Close
DMD_SW2L
Open
IAQ.L
IAQ Disc.Input - Low
Open/Close
IAQINLOG
Open
FSD.L
Fire Shutdown - Off
Open/Close
FSDLOGIC
Open
PRS.L
Pressurization Sw. - Off
Open/Close
PRESLOGC
Open
EVC.L
Evacuation Sw. - Off
Open/Close
EVACLOGC
Open
PRG.L
Smoke Purge Sw. - Off
Open/Close
PURGLOGC
Open
ITEM
EXPANSION
RANGE
UNITS
POINT
DEFAULT
TEST
Test Display LEDs
ON/OFF
TEST
Off
METR
Metric Display
ON/OFF
DISPUNIT
Off
LANG
Language Selection
0-1(multi-text strings)
LANGUAGE
0
PAS.E
Password Enable
ENABLE/DISABLE
PASS_EBL
Enable
PASS
Service Password
0000-9999
PASSWORD
1111
ITEM
EXPANSION
RANGE
CCN
POINT
REMT
Remote Input State
ON/OFF
RMTIN
RM.CF
Remote Switch Config 0 - 3
RMTINCFG
RMI.L
RemSw
Off-Unoc-Strt-NoOv
Open/Close
RMTINLOG
ITEM
EXPANSION
RANGE
UNITS
CCN
POINT
SP.O.S
Space Temp
Offset Sensor
Enable/
Disable
SPTOSENS
SP.O.R
Space Temp
Offset Range
1 - 10
SPTO_RNG
SPTO
Space Temperature
Offset
+-
SP.O.R
^F
SPTO
Содержание WEATHERMAKER 48/50AJ
Страница 103: ...103 Fig 15 Typical Main Control Box Wiring Schematic 48 50AJ AK AW AY Units cont a48 8355 ...
Страница 104: ...104 Fig 16 Typical Main Control Box Wiring Schematic 48 50A2 A3 A4 A5 Units a48 8355 ...
Страница 105: ...105 TO NEXT PAGE Fig 17 Typical Auxiliary Control Box Wiring Schematic A48 7294 ...
Страница 106: ...106 Fig 17 Typical Auxiliary Control Box Wiring Schematic cont a48 8356 ...
Страница 107: ...107 Fig 18 Typical 2 Stage Gas Heat Wiring Schematic Size 051 and 060 Units Shown a48 8357 ...
Страница 108: ...108 TO NEXT PAGE Fig 19 Typical Staged Gas Heat Wiring Schematic Size 051 and 060 Units Shown A48 7296 ...
Страница 109: ...109 Fig 19 Typical Staged Gas Heat Wiring Schematic Size 051 and 060 Units Shown cont A48 8358 ...
Страница 110: ...110 Fig 20 Typical Electric Heat Control Schematic 50 Series Size 051 and 060 Units Shown a50 8228 ...
Страница 111: ...111 TO NEXT PAGE Fig 21 Typical Power Schematic 48 50AJ AK AW AY051 and 060 Units Shown A48 7298 ...
Страница 112: ...112 FROM PREVIOUS PAGE Fig 21 Typical Power Schematic 48 50AJ AK AW AY051 and 060 Units Shown cont a48 8360 ...
Страница 113: ...113 Fig 22 Typical Power Schematic 48 50A2 A3 A4 A5060 Unit Shown ...
Страница 114: ...114 SW1 SW2 OR DEHUMIDIFY SWITCH Fig 23 Typical Controls Option Wiring Schematic a48 8361 ...
Страница 115: ...115 Fig 24 Typical Small Chassis Component Location Size 020 035 Units a48 8362 ...
Страница 116: ...116 Fig 25 Typical Large Chassis Component Locations Size 036 060 Units A48 7302 ...
Страница 169: ...169 APPENDIX C VFD INFORMATION cont Fig F Internal Enclosure Fan Replacement A48 7716 ...