152
APPENDIX B — CCN TABLES (cont)
CONFIG TABLES (cont)
SERVICE-CONFIG TABLES
TABLE
NAME
RANGE
UNITS
POINT NAME
DEFAULT
SCHEDOVR
Schedule Number
0-99
SCHEDNUM
0
Accept Global Holidays?
Yes/No
HOLIDAYT
No
Override Time Limit
0-4
hours
OTL
1
Timed Override Hours
0-4
hours
OVR_EXT
0
Accepting an Override:
SPT Override Enabled ?
Yes/No
SPT_OVER
Yes
T58 Override Enabled ?
Yes/No
T58_OVER
Yes
Allowed to Broadcast a
Global Sched. Override ?
Yes/No
GLBLOVER
No
SET_PNT
Occupied Heat Setpoint
55-80
dF
OHSP
68
Occupied Cool Setpoint
55-80
dF
OCSP
75
Unoccupied Heat Setpoint
40-80
dF
UHSP
55
Unoccupied Cool Setpoint
75-95
dF
UCSP
90
Heat-Cool Setpoint Gap
2-10
^F
HCSP_GAP
5
VAV Occ. Cool On Delta
0-25
^F
VAVOCON
3.5
VAV Occ. Cool Off Delta
1-25
^F
VAVOCOFF
2
Supply Air Setpoint
45-75
dF
SASP
55
Supply Air Setpoint Hi
45-75
dF
SASP_HI
55
Supply Air Setpoint Lo
45-75
dF
SASP_LO
60
Heating Supply Air Setpt
90-145
dF
SASPHEAT
85
Tempering Purge SASP
–20-80
dF
TEMPPURG
50
TABLE
NAME
RANGE
UNITS
POINT NAME
DEFAULT
ALLM
SPT lo alert limit/occ
–10-245
dF
SPLO
60
SPT hi alert limit/occ
–10-245
dF
SPHO
85
SPT lo alert limit/unocc
–10-245
dF
SPLU
45
SPT hi alert limit/unocc
–10-245
dF
SPHU
100
EDT lo alert limit/occ
–40-245
dF
SALO
40
EDT hi alert limit/occ
–40-245
dF
SAHO
100
EDT lo alert limit/unocc
–40-245
dF
SALU
40
EDT hi alert limit/unocc
–40-245
dF
SAHU
100
RAT lo alert limit/occ
–40-245
dF
RALO
60
RAT hi alert limit/occ
–40-245
dF
RAHO
90
RAT lo alert limit/unocc
–40-245
dF
RALU
40
RAT hi alert limit/unocc
–40-245
dF
RAHU
100
RARH low alert limit
0-100
%
RRHL
0
RARH high alert limit
0-100
%
RRHH
100
SP low alert limit
0-5
"H2O
SPL
0
SP high alert limit
0-5
"H2O
SPH
2
BP lo alert limit
–0.25-0.25
"H2O
BPL
-0.25
BP high alert limit
–0.25-0.25
"H2O
BPH
0.25
IAQ high alert limit
0-5000
IAQH
1200
BP__
Building Press. Config
0-3
BLDG_CFG
0
Bldg.Pres.PID Run Rate
5-120
BPIDRATE
10
Bldg. Press. Prop. Gain
0-5
BLDGP_PG
0.5
Bldg.Press.Integ.Gain
0-2
BLDGP_IG
0.5
Bldg.Press.Deriv.Gain
0-5
BLDGP_DG
0.3
BP Setpoint Offset
0.0 - 0.5
BPSO
0.05
BP VFD Minimum Speed
0-100
BLDGPMIN
10
BP VFD Maximum Speed
0-100
BLDGPMAX
100
VFD/Act. Fire Speed/Pos.
0-100
BLDGPFSO
100
Power Exhaust Motors
0-2
PWRM
1
0=None,1=4 Mtr, 2=6 Mtr
Building Pressure Sensor
Enable/Disable
BPSENS
Dsable
Bldg Press (+/-) Range
0-1
BP_RANGE
0.25
Building Pressure Setp.
–0.25 -> 0.25
"H2O
BPSP
0.05
Power Exhaust On Setp.1
0-100
%
PES1
35
Power Exhaust On Setp.2
0-100
%
PES2
75
Modulating PE Alg. Slct.
1-3
BPSELECT
1
BP PID Evaluation Time
0-10
min
BPPERIOD
1
BP Threshold Adjustment
0.1-10
BPZ_GAIN
1
High BP Level
0-1
BPHPLVL
0.05
Low BP Level
0-1
BPLPLVL
0.04
Содержание WEATHERMAKER 48/50AJ
Страница 103: ...103 Fig 15 Typical Main Control Box Wiring Schematic 48 50AJ AK AW AY Units cont a48 8355 ...
Страница 104: ...104 Fig 16 Typical Main Control Box Wiring Schematic 48 50A2 A3 A4 A5 Units a48 8355 ...
Страница 105: ...105 TO NEXT PAGE Fig 17 Typical Auxiliary Control Box Wiring Schematic A48 7294 ...
Страница 106: ...106 Fig 17 Typical Auxiliary Control Box Wiring Schematic cont a48 8356 ...
Страница 107: ...107 Fig 18 Typical 2 Stage Gas Heat Wiring Schematic Size 051 and 060 Units Shown a48 8357 ...
Страница 108: ...108 TO NEXT PAGE Fig 19 Typical Staged Gas Heat Wiring Schematic Size 051 and 060 Units Shown A48 7296 ...
Страница 109: ...109 Fig 19 Typical Staged Gas Heat Wiring Schematic Size 051 and 060 Units Shown cont A48 8358 ...
Страница 110: ...110 Fig 20 Typical Electric Heat Control Schematic 50 Series Size 051 and 060 Units Shown a50 8228 ...
Страница 111: ...111 TO NEXT PAGE Fig 21 Typical Power Schematic 48 50AJ AK AW AY051 and 060 Units Shown A48 7298 ...
Страница 112: ...112 FROM PREVIOUS PAGE Fig 21 Typical Power Schematic 48 50AJ AK AW AY051 and 060 Units Shown cont a48 8360 ...
Страница 113: ...113 Fig 22 Typical Power Schematic 48 50A2 A3 A4 A5060 Unit Shown ...
Страница 114: ...114 SW1 SW2 OR DEHUMIDIFY SWITCH Fig 23 Typical Controls Option Wiring Schematic a48 8361 ...
Страница 115: ...115 Fig 24 Typical Small Chassis Component Location Size 020 035 Units a48 8362 ...
Страница 116: ...116 Fig 25 Typical Large Chassis Component Locations Size 036 060 Units A48 7302 ...
Страница 169: ...169 APPENDIX C VFD INFORMATION cont Fig F Internal Enclosure Fan Replacement A48 7716 ...