177
APPENDIX E — UPC OPEN CONTROLLER (cont)
NETWORK POINTS LIST (cont)
See legend on page 182.
BACNET
OBJECT ID
POINT NAME
READ
ONLY
UNITS
DEFAULT
VALUE
RANGE
BACNET
OBJECT NAME
UNIT
POINT
AV:61
Dmd Level(+) Hi Cool ON
W
°^F
0.5
0.5-20
dmdhcon_1
DMDHCON
AV:62
Dmd Level(+) Hi Heat ON
W
°^F
0.5
0.5-20
dmdhhon_1
DMDHHON
AV:63
Dmd Level Low Cool ON
W
°^F
1.5
0.5-2
dmdlcon_1
DMDLCON
AV:64
Dmd Level Low Heat ON
W
°^F
1.5
0.5-2
dmdlhon_1
DMDLHON
AV:66
Econo Current Min. Pos.
R
%
n/a
n/a
min_pos_1
MIN_POS
AV:67
Economizer Act. Cmd. Pos.
W
%
n/a
0-100
econocmd_1
ECONOCMD
AV:68
Economizer Control Point
R
°F
n/a
n/a
econpnt_1
ECONCPNT
AV:70
Economizer Max.Position
W
%
98
0-100
economax_1
ECONOMAX
AV:76
Evaporator Discharge Tmp
R
°F
n/a
n/a
edt_1
EDT
AV:77
Fan Mode
W
n/a
1
0-1
fan_mode_1
FAN_MODE
AV:78
Fan-Off Delay, Elec Heat
W
n/a
30
10-600
elec_fod_1
ELEC_FOD
AV:79
Fan-Off Delay, Gas Heat
W
n/a
45
45-600
gas_fod_1
GAS_FOD
AV:80
Fan-Off Delay, Mech Cool
W
sec
60
0-600
cool_fod_1
COOL_FOD
AV:83
Heat-Cool Setpoint Gap
W
°^F
5
2-10
hcsp_gap_1
HCSP_GAP
AV:85
Heating Supply Air Setpt
W
°F
85
80-120
saspheat_1
SASPHEAT
AV:86
High BP Level
W
n/a
0.05
0-1
bphplvl_1
BPHPLVL
AV:87
Low BP Level
W
n/a
0.04
0-1
bplplvl_1
BPLPLVL
AV:93
IAQ Econo Override Pos.
W
%
100
0-100
iaqovpos_1
IAQOVPOS
AV:95
IAQ High Reference
W
n/a
2000
0-5000
iaqrefh_1
IAQREFH
AV:96
IAQ Low Reference
W
n/a
0
0-5000
iaqrefl_1
IAQREFL
AV:97
IAQ Min.Pos.Override
W
%
n/a
0-100
iaqminov_1
IAQMINOV
AV:98
IAQ Purge Duration
W
min
15
5-60
iaqptime_1
IAQPTIME
AV:99
IAQ Purge HiTemp Min Pos
W
%
35
0-100
iaqphtmp_1
IAQPHTMP
AV:100
IAQ Purge LoTemp Min Pos
W
%
10
0-100
iaqpltmp_1
IAQPLTMP
AV:101
IAQ Purge OAT Lockout
W
°F
50
35-70
iaqpntlo_1
IAQPNTLO
AV:102
LAT Limit Config
W
°^F
10
0-20
htlatlim_1
HTLATLIM
AV:107
Maximum Heat Stages
R
n/a
n/a
n/a
htmaxstg_1
HTMAXSTG
AV:112
OAQ Lockout Value
W
n/a
0
0-2000
oaqlock_1
OAQLOCK
AV:113
OAQ - PPM Outdoor CO2
W
n/a
n/a
0-5000
oaq_1
OAQ
AV:114
Occupied Cool Mode End
R
°F
n/a
n/a
occl_end_1
OCCL_END
AV:115
Occupied Cool Mode Start
R
°F
n/a
n/a
occlstrt_1
OCCLSTRT
AV:116
Occupied Heat Mode End
R
°F
n/a
n/a
ocht_end_1
OCHT_END
AV:117
Occupied Heat Mode Start
R
°F
n/a
n/a
ochtstrt_1
OCHTSTRT
AV:118
Outside Air Humidity Ratio
R
n/a
n/a
n/a
oa_humr_1
OA_HUMR
AV:119
Outside Air Relative Humidity
W
%
n/a
0-100
oarh_1
OARH
AV:120
Override Time Limit
W
hr
1
0-4
otl_1
OTL
AV:121
Power Exhaust Motors
W
n/a
1
0-2
pwrm_1
PWRM
AV:122
Power Exhaust On Setp.1
W
%
35
0-100
pes1_1
PES1
AV:123
Power Exhaust On Setp.2
W
%
75
0-100
pes2_1
PES2
AV:130
Remote Switch Config
W
n/a
0
0-3
rmtincfg_1
RMTINCFG
AV:131
Reset Limit
W
°^F
10
0-20
limt_1
LIMT
AV:132
Reset Ratio
W
n/a
2
0-10
rtio_1
RTIO
AV:133
Return Air Enthalpy
R
n/a
n/a
n/a
rae_1
RAE
Содержание WEATHERMAKER 48/50AJ
Страница 103: ...103 Fig 15 Typical Main Control Box Wiring Schematic 48 50AJ AK AW AY Units cont a48 8355 ...
Страница 104: ...104 Fig 16 Typical Main Control Box Wiring Schematic 48 50A2 A3 A4 A5 Units a48 8355 ...
Страница 105: ...105 TO NEXT PAGE Fig 17 Typical Auxiliary Control Box Wiring Schematic A48 7294 ...
Страница 106: ...106 Fig 17 Typical Auxiliary Control Box Wiring Schematic cont a48 8356 ...
Страница 107: ...107 Fig 18 Typical 2 Stage Gas Heat Wiring Schematic Size 051 and 060 Units Shown a48 8357 ...
Страница 108: ...108 TO NEXT PAGE Fig 19 Typical Staged Gas Heat Wiring Schematic Size 051 and 060 Units Shown A48 7296 ...
Страница 109: ...109 Fig 19 Typical Staged Gas Heat Wiring Schematic Size 051 and 060 Units Shown cont A48 8358 ...
Страница 110: ...110 Fig 20 Typical Electric Heat Control Schematic 50 Series Size 051 and 060 Units Shown a50 8228 ...
Страница 111: ...111 TO NEXT PAGE Fig 21 Typical Power Schematic 48 50AJ AK AW AY051 and 060 Units Shown A48 7298 ...
Страница 112: ...112 FROM PREVIOUS PAGE Fig 21 Typical Power Schematic 48 50AJ AK AW AY051 and 060 Units Shown cont a48 8360 ...
Страница 113: ...113 Fig 22 Typical Power Schematic 48 50A2 A3 A4 A5060 Unit Shown ...
Страница 114: ...114 SW1 SW2 OR DEHUMIDIFY SWITCH Fig 23 Typical Controls Option Wiring Schematic a48 8361 ...
Страница 115: ...115 Fig 24 Typical Small Chassis Component Location Size 020 035 Units a48 8362 ...
Страница 116: ...116 Fig 25 Typical Large Chassis Component Locations Size 036 060 Units A48 7302 ...
Страница 169: ...169 APPENDIX C VFD INFORMATION cont Fig F Internal Enclosure Fan Replacement A48 7716 ...