146
APPENDIX A — LOCAL DISPLAY TABLES (cont)
MODE — CONFIGURATION (cont)
ITEM
EXPANSION
RANGE
UNITS
CCN POINT
DEFAULT
PAGE NO.
CCN
CCN CONFIGURATION
CCNA
CCN Address
1 - 239
CCNADD
1
71,72
CCNB
CCN Bus Number
0 - 239
CCNBUS
0
71,72
BAUD
CCN Baud Rate
1 - 5 (multi-text strings)
CCNBAUDD
3
71,72
BROD
CCN BROADCST DEFINITIONS
BROD
TM.DT
CCN Time/Date Broadcast
ON/OFF
CCNBC
On
71,72
BROD
OAT.B
CCN OAT Broadcast
ON/OFF
OATBC
Off
71,72
BROD
ORH.B
CCN OARH Broadcast
ON/OFF
OARHBC
Off
71,72
BROD
OAQ.B
CCN OAQ Broadcast
ON/OFF
OAQBC
Off
71,72
BROD
G.S.B
Global Schedule Broadcst
ON/OFF
GSBC
Off
71,72
BROD
B.ACK
CCN Broadcast Ack'er
ON/OFF
CCNBCACK
Off
71,72
SC.OV
CCN SCHEDULES-OVERRIDES
SC.OV
SCH.N
Schedule Number
0 - 99
SCHEDNUM
1
27-29,71,72
SC.OV
HOL.T
Accept Global Holidays?
YES/NO
HOLIDAYT
No
72
SC.OV
O.T.L.
Override Time Limit
0 - 4
HRS
OTL
1
27,72
SC.OV
OV.EX
Timed Override Hours
0 - 4
HRS
OVR_EXT
0
72
SC.OV
SPT.O
SPT Override Enabled ?
YES/NO
SPT_OVER
Yes
27,72
SC.OV
T58.O
T58 Override Enabled ?
YES/NO
T58_OVER
Yes
27,72
SC.OV
GL.OV
Global Sched. Override ?
YES/NO
GLBLOVER
No
72
ALLM
ALERT LIMIT CONFIG.
SP.L.O
SPT lo alert limit/occ
–10-245
dF
SPLO
60
72,73,98
SP.H.O
SPT hi alert limit/occ
–10-245
dF
SPHO
85
72,73,99
SP.L.U
SPT lo alert limit/unocc
–10-245
dF
SPLU
45
72,73,98
SP.H.U
SPT hi alert limit/unocc
–10-245
dF
SPHU
100
72,73,99
SA.L.O
EDT lo alert limit/occ
–40-245
dF
SALO
40
43,72,73,99
SA.H.O
EDT hi alert limit/occ
–40-245
dF
SAHO
100
72,73,99
SA.L.U
EDT lo alert limit/unocc
–40-245
dF
SALU
40
72,73,99
SA.H.U
EDT hi alert limit/unocc
–40-245
dF
SAHU
100
72,73,99
RA.L.O
RAT lo alert limit/occ
–40-245
dF
RALO
60
72,73,99
RA.H.O
RAT hi alert limit/occ
–40-245
dF
RAHO
90
72,73,99
RA.L.U
RAT lo alert limit/unocc
–40-245
dF
RALU
40
72,73,99
RA.H.U
RAT hi alert limit/unocc
–40-245
dF
RAHU
100
72,73,99
R.RH.L
RARH low alert limit
0-100
%
RRHL
0
72,73,99
R.RH.H
RARH high alert limit
0-100
%
RRHH
100
72,73,99
SP.L
SP low alert limit
0-5
"H2O
SPL
0
73,99
SP.H
SP high alert limit
0-5
"H2O
SPH
2
73,99
BP.L
BP lo alert limit
–0.25-0.25
"H2O
BPL
-0.25
73,99
BP.H
BP high alert limit
–0.25-0.25
"H2O
BPH
0.25
73,99
IAQ.H
IAQ high alert limit
0-5000
IAQH
1200
73,99
TRIM
SENSOR TRIM CONFIG.
SAT.T
Air Temp Lvg SF Trim
–10 - 10
^F
SAT_TRIM
0
73
RAT.T
RAT Trim
–10 - 10
^F
RAT_TRIM
0
73
OAT.T
OAT Trim
–10 - 10
^F
OAT_TRIM
0
73
SPT.T
SPT Trim
–10 - 10
^F
SPT_TRIM
0
73
CTA.T
Cir A Sat.Cond.Temp Trim
–30 - 30
^F
SCTATRIM
0
73
CTB.T
Cir B Sat.Cond.Temp Trim
–30 - 30
^F
SCTBTRIM
0
73
SP.A.T
Suct.Press.Circ.A Trim
–50 - 50
PSIG
SPA_TRIM
0
73
SP.B.T
Suct.Press.Circ.B Trim
–50 - 50
PSIG
SPB_TRIM
0
73
DP.A.T
Dis.Press.Circ.A Trim
–50 - 50
PSIG
DPA_TRIM
0
73,74
DP.B.T
Dis.Press.Circ.B Trim
–50 - 50
PSIG
DPB_TRIM
0
73,74
SW.LG
SWITCH LOGIC: NO / NC
FTS.L
Filter Status Inpt-Clean
Open/Close
FLTSLOGC
Open
74,75
IGC.L
IGC Feedback - Off
Open/Close
GASFANLG
Open
74,75
RMI.L
RemSw Off-Unoc-Strt-NoOv
Open/Close
RMTINLOG
Open
31,74,75
ECS.L
Economizer Switch - No
Open/Close
ECOSWLOG
Open
74,75
SFS.L
Fan Status Sw. - Off
Open/Close
SFSLOGIC
Open
74,75,100
DL1.L
Dmd.Lmt.Sw.1 - Off
Open/Close
DMD_SW1L
Open
31,74,75
DL2.L
Dmd.Lmt.Sw.2 - Dehumid - Off
Open/Close
DMD_SW2L
Open
31,74,75
IAQ.L
IAQ Disc.Input - Low
Open/Close
IAQINLOG
Open
31,32,74,75
FSD.L
Fire Shutdown - Off
Open/Close
FSDLOGIC
Open
74,75,99
PRS.L
Pressurization Sw. - Off
Open/Close
PRESLOGC
Open
74,75
EVC.L
Evacuation Sw. - Off
Open/Close
EVACLOGC
Open
74,75
PRG.L
Smoke Purge Sw. - Off
Open/Close
PURGLOGC
Open
74,75
DISP
DISPLAY CONFIGURATION
TEST
Test Display LEDs
ON/OFF
TEST
Off
74,75
METR
Metric Display
ON/OFF
DISPUNIT
Off
74,75
LANG
Language Selection
0-1(multi-text strings)
LANGUAGE
0
74,75
PAS.E
Password Enable
ENABLE/DISABLE
PASS_EBL
Enable
74,75
PASS
Service Password
0000-9999
PASSWORD
1111
74,75
Содержание WEATHERMAKER 48/50AJ
Страница 103: ...103 Fig 15 Typical Main Control Box Wiring Schematic 48 50AJ AK AW AY Units cont a48 8355 ...
Страница 104: ...104 Fig 16 Typical Main Control Box Wiring Schematic 48 50A2 A3 A4 A5 Units a48 8355 ...
Страница 105: ...105 TO NEXT PAGE Fig 17 Typical Auxiliary Control Box Wiring Schematic A48 7294 ...
Страница 106: ...106 Fig 17 Typical Auxiliary Control Box Wiring Schematic cont a48 8356 ...
Страница 107: ...107 Fig 18 Typical 2 Stage Gas Heat Wiring Schematic Size 051 and 060 Units Shown a48 8357 ...
Страница 108: ...108 TO NEXT PAGE Fig 19 Typical Staged Gas Heat Wiring Schematic Size 051 and 060 Units Shown A48 7296 ...
Страница 109: ...109 Fig 19 Typical Staged Gas Heat Wiring Schematic Size 051 and 060 Units Shown cont A48 8358 ...
Страница 110: ...110 Fig 20 Typical Electric Heat Control Schematic 50 Series Size 051 and 060 Units Shown a50 8228 ...
Страница 111: ...111 TO NEXT PAGE Fig 21 Typical Power Schematic 48 50AJ AK AW AY051 and 060 Units Shown A48 7298 ...
Страница 112: ...112 FROM PREVIOUS PAGE Fig 21 Typical Power Schematic 48 50AJ AK AW AY051 and 060 Units Shown cont a48 8360 ...
Страница 113: ...113 Fig 22 Typical Power Schematic 48 50A2 A3 A4 A5060 Unit Shown ...
Страница 114: ...114 SW1 SW2 OR DEHUMIDIFY SWITCH Fig 23 Typical Controls Option Wiring Schematic a48 8361 ...
Страница 115: ...115 Fig 24 Typical Small Chassis Component Location Size 020 035 Units a48 8362 ...
Страница 116: ...116 Fig 25 Typical Large Chassis Component Locations Size 036 060 Units A48 7302 ...
Страница 169: ...169 APPENDIX C VFD INFORMATION cont Fig F Internal Enclosure Fan Replacement A48 7716 ...