143
APPENDIX A — LOCAL DISPLAY TABLES (cont)
MODE — INPUTS (cont)
*The display text changes depending on the remote switch configuration (
Configuration
UNIT
RM.CF
). If
RM.CF
is set to 0 (No Remote
Switch), then the display text will be “On” or “Off.” If
RM.CF
is set to 1 (Occupied/Unoccupied Switch), then the display text will be “Occupied” or
“Unoccupied.” If
RM.CF
is set to 2 (Start/Stop), then the display text will be “Stop” or “Start.” If
RM.CF
is set to 3 (Override Switch), then the display
text will be “No Override” or “Override.”
MODE — OUTPUTS
MODE — CONFIGURATION
ITEM
EXPANSION
RANGE
UNITS
CCN POINT
WRITE STATUS
4-20
4-20 MILLIAMP INPUTS
IAQ.M
IAQ Milliamps
ma
IAQ_MA
OAQ.M
OAQ Milliamps
ma
OAQ_MA
SP.R.M
SP Reset milliamps
ma
SPRST_MA
DML.M
4-20 ma Demand Signal
ma
DMDLMTMA
forcible
EDR.M
EDT Reset Milliamps
ma
EDTRESMA
ORH.M
OARH Milliamps
ma
OARH_MA
RRH.M
RARH Milliamps
ma
RARH_MA
BP.M
BP Milliamps
ma
BP_MA
BP.M.T
Bldg. Pressure Trim (ma)
–2.0 - 2.0
BPMATRIM
config
SP.M
SP Milliamps
ma
SP_MA
SP.M.T
Static Press. Trim (ma)
–2.0 - 2.0
SPMATRIM
config
ITEM
EXPANSION
RANGE
UNITS
CCN POINT
WRITE STATUS
FANS
FANS
S.FAN
Supply Fan Relay
ON/OFF
SFAN_RLY
S.VFD
Supply Fan VFD Speed
0-100
%
SFAN_VFD
P.E.A
Power Exhaust Relay A
ON/OFF
PE_A
P.E.B
Power Exhaust Relay B
ON/OFF
PE_B
P.E.C
Power Exhaust Relay C
ON/OFF
PE_C
CD.F.A
Condenser Fan Circuit A
ON/OFF
CONDFANA
CD.F.B
Condenser Fan Circuit B
ON/OFF
CONDFANB
COOL
COOLING
A1
Compressor A1 Relay
ON/OFF
CMPA1
A2
Compressor A2 Relay
ON/OFF
CMPA2
MLV
Min. Load Valve (HGBP)
ON/OFF
MLV
B1
Compressor B1 Relay
ON/OFF
CMPB1
B2
Compressor B2 Relay
ON/OFF
CMPB2
HEAT
HEATING
HT.1
Heat Relay 1
ON/OFF
HS1
HT.2
Heat Relay 2
ON/OFF
HS2
HT.3
Relay 3 W1 Gas Valve 2
ON/OFF
HS3
HT.4
Relay 4 W2 Gas Valve 2
ON/OFF
HS4
HT.5
Relay 5 W1 Gas Valve 3
ON/OFF
HS5
HT.6
Relay 6 W2 Gas Valve 3
ON/OFF
HS6
H.I.R
Heat Interlock Relay
ON/OFF
HIR
forcible
ECON
ECONOMIZER
ECN.P
Economizer Act.Curr.Pos.
0-100
%
ECONOPOS
ECN.C
Economizer Act.Cmd.Pos.
0-100
%
ECONOCMD
forcible
E.PWR
Economizer Power Relay
ON/OFF
ECON_PWR
forcible
GEN.O
GENERAL OUTPUTS
ALRM
Remote Alarm/Aux Relay
ON/OFF
ALRM
forcible
ITEM
EXPANSION
RANGE
UNITS
CCN POINT
DEFAULT
PAGE NO.
UNIT
UNIT CONFIGURATION
C.TYP
Machine Control Type
1 - 6 (multi-text strings)
CTRLTYPE
4
27,28,32,35-37,
63,75,96
CV.FN
Fan Mode (0=Auto, 1=Cont)
0 - 1 (multi-text strings)
FAN_MODE
1
27,28,35,36
RM.CF
Remote Switch Config
0 - 3 (multi-text strings)
RMTINCFG
0
31,35,36,74
CEM
CEM Module Installed
Yes/No
CEM_BRD
No
35,36
TCS.C
Temp.Cmp.Strt.Cool Factr
0 - 60
min
TCSTCOOL
0
35,36
TCS.H
Temp.Cmp.Strt.Heat Factr
0 - 60
min
TCSTHEAT
0
36
SFS.S
Fan Fail Shuts Down Unit
Yes/No
SFS_SHUT
No
36,60,100
SFS.M
Fan Stat Monitoring Type
0 - 2 (multi-text strings)
SFS_MON
0
35,36,60,100
VAV.S
VAV Unocc.Fan Retry Time
0 - 720
min
SAMPMINS
50
36
SIZE
Unit Size (20-60)
20 - 60
UNITSIZE
20
36,38,42,49
DP.XR
Disch.Press. Transducers
Yes/No
DP_TRANS
No
36,97
SP.XR
Suct. Pres. Trans. Type
0 - 1 (multi-text strings)
SPXRTYPE
0
36
RFG.T
Refrig: 0=R22 1=R410A
0 - 1 (multi-text strings)
REFRIG_T
1
36,38,49
CND.T
Cnd HX Typ:0=RTPF 1=MCHX
0 - 1 (multi-text strings)
COILTYPE
0
36,38,49
MAT.S
MAT Calc Config
0 - 2 (multi-text strings)
MAT_SEL
1
36,47,48
MAT.R
Reset MAT Table Entries?
Yes/No
MATRESET
No
36,47,48
MAT.D
MAT Outside Air Default
0-100
%
MATOADOS
20
36,37
ALTI
Altitude……..in feet:
0 - 60000
ALTITUDE
0
36,37
DLAY
Startup Delay Time
0 - 900
sec
DELAY
0
36,37
STAT
TSTAT-Both Heat and Cool
Yes/No
TSTATALL
No
36,37
AUX.R
Auxiliary Relay Config
0 - 3
AUXRELAY
0
36,37
SENS
INPUT SENSOR CONFIG
36
SENS
SPT.S
Space Temp Sensor
Enable/Disable
SPTSENS
Disable
27,28,36,37
SENS
SP.O.S
Space Temp Offset Sensor
Enable/Disable
SPTOSENS
Disable
36,37,75
SENS
SP.O.R
Space Temp Offset Range
1 - 10
SPTO_RNG
5
36,37,75
SENS
RRH.S
Return Air RH Sensor
Enable/Disable
RARHSENS
Disable
36,37,61,97,99
SENS
FLT.S
Filter Stat.Sw.Enabled ?
Enable/Disable
FLTS_ENA
Disable
36,37,60,100
Содержание WEATHERMAKER 48/50AJ
Страница 103: ...103 Fig 15 Typical Main Control Box Wiring Schematic 48 50AJ AK AW AY Units cont a48 8355 ...
Страница 104: ...104 Fig 16 Typical Main Control Box Wiring Schematic 48 50A2 A3 A4 A5 Units a48 8355 ...
Страница 105: ...105 TO NEXT PAGE Fig 17 Typical Auxiliary Control Box Wiring Schematic A48 7294 ...
Страница 106: ...106 Fig 17 Typical Auxiliary Control Box Wiring Schematic cont a48 8356 ...
Страница 107: ...107 Fig 18 Typical 2 Stage Gas Heat Wiring Schematic Size 051 and 060 Units Shown a48 8357 ...
Страница 108: ...108 TO NEXT PAGE Fig 19 Typical Staged Gas Heat Wiring Schematic Size 051 and 060 Units Shown A48 7296 ...
Страница 109: ...109 Fig 19 Typical Staged Gas Heat Wiring Schematic Size 051 and 060 Units Shown cont A48 8358 ...
Страница 110: ...110 Fig 20 Typical Electric Heat Control Schematic 50 Series Size 051 and 060 Units Shown a50 8228 ...
Страница 111: ...111 TO NEXT PAGE Fig 21 Typical Power Schematic 48 50AJ AK AW AY051 and 060 Units Shown A48 7298 ...
Страница 112: ...112 FROM PREVIOUS PAGE Fig 21 Typical Power Schematic 48 50AJ AK AW AY051 and 060 Units Shown cont a48 8360 ...
Страница 113: ...113 Fig 22 Typical Power Schematic 48 50A2 A3 A4 A5060 Unit Shown ...
Страница 114: ...114 SW1 SW2 OR DEHUMIDIFY SWITCH Fig 23 Typical Controls Option Wiring Schematic a48 8361 ...
Страница 115: ...115 Fig 24 Typical Small Chassis Component Location Size 020 035 Units a48 8362 ...
Страница 116: ...116 Fig 25 Typical Large Chassis Component Locations Size 036 060 Units A48 7302 ...
Страница 169: ...169 APPENDIX C VFD INFORMATION cont Fig F Internal Enclosure Fan Replacement A48 7716 ...