![CARLO GAVAZZI VariFlex3 RVFFA3400400F Скачать руководство пользователя страница 93](http://html1.mh-extra.com/html/carlo-gavazzi/variflex3-rvffa3400400f/variflex3-rvffa3400400f_quick-start-manual_2558654093.webp)
Motor Controllers AC Variable Frequency Drives
Type Variflex
3
RVFF
Specifications are subjected to change without notice.
92
5.8 Routine and periodic inspection
To ensure stable and safe operations, check and maintain the inverter at regular intervals. Use the checklist
below to carry out inspection. Disconnect power after approximately 5 minutes to make sure no voltage is
present on the output terminals before any inspection or maintenance.
Items
Details
Checking
period
Methods
Criteria
Remedies
Daily 1Year
Environment & Ground connection
Ambient
conditions at
the
installation
Confirm the temperature
and humidity at the
machine
◎
Measure
with
thermometer
and
hygrometer
Temperature:
-10 ~40°C/50°C
(14~104°F)/(122°F)
Humidity: Below
95%RH
Improve the
ambient or
relocate the
drive to a
better area.
Installation
Grounding
Is the grounding
resistance correct?
◎
Measure the
resistance
with a multi-
tester
200Vclass: below
100Ω
Improve the
grounding if
needed.
Terminals & Wiring
Connection
terminals
Any loose parts or
terminals?
◎
Visual check
Check with
a
screwdriver
Correct installation
requirement
Secure
terminals
and remove
rust
Any damage to the
base?
◎
Any corroded
Terminals?
◎
Wiring
Any broken wires?
◎
Visual check
Correct wiring
requirement
Rectify as
necessary
Any damage to the wire
insulation?
◎
Voltage
Input power
voltage
Is the voltage of the
main circuit correct?
◎
Measure the
voltage with
a multi-
tester
Voltage must
conform with the
spec.
Improve
input
voltage if
necessary.
Circuit boards and components
Printed
circuit board
Any contamination or
damage to printed circuit
board?
◎
Visual check
Correct component
condition
Clean or
replace the
circuit board
Power
component
Any dust or debris
◎
Clean
components
Check resistance
between terminals
◎
Measure
with a multi-
tester
No short circuit or
broken circuit in
three phase output
Consult
with the
supplier
Cooling System
Cooling fan
Unusual vibration and
noise?
◎
Visual and
sound check
Correct cooling
Consult
with the
supplier
Excessive dust or debris
◎
Visual check
Clean the
fan
Heat sink
Excessive dust or debris
◎
Clean up
debris or
dust
Ventilation
Path
Is the ventilation path
blocked?
◎
Clear the
path
Содержание VariFlex3 RVFFA3400400F