LED
display
Description
Cause
Possible solutions
HFPB
High flow
error
High flow error
•
Due to HVAC feedback value is lower
than limit of maximum flow.
•
Check feedback signal is
correct.
•
Check if feedback value is
lower than limit of maximum
flow.
L0PB
Low
pressure
error
Low pressure error
•
The feedback signal is not connected.
•
Due to feedback value of pump
pressure is lower than limit of
minimum flow.
•
Check feedback signal is
correct and with connection.
•
Check if feedback value of
pressure is lower than limit of
minimum pressure.
HIPB
High
pressure
error
High pressure error
•
Due to feedback value of pump
pressure is lower than limit of
maximum flow.
•
Check feedback signal is
correct.
•
Check if feedback value of
pressure is lower than limit of
maximum pressure.
LSCFT
Low
suction
error
Inadequate suction
error
•
Insufficient water of supply tank leads
to insufficient suction.
•
PID difference is higher than its level
or current is lower than output current
level.
•
Check if water of supply tank
is enough, and water supply
is regular.
•
Check PID difference is
higher than its level or current
is lower than output current
level
FIRE
Fire
override
mode
Fire override mode
•
Fire override mode is active
•
None
•
(Fire override mode is not a
kind of warning).
SE10
PUMP/HVA
C
Setting
error
PUMP/HVAC
settings of inverter
error
•
PUMP
selection
of
inverter
(23-02)>(23-03).
•
HVAC
selection
of
inverter
(23-46)>(23-47).
•
Check pump selection of
inverter (23-02) and (23-03)
settings.
•
Check HVAC selection of
inverter (23-02) and (23-03)
settings.
COPUP
PUMP
communica
tion
breaking
error
Breaking error of
multiple pumps
communication
•
Communication breaking or
disconnection of pump cascade
control.
•
Check if it has setting issue or