Group 11 Auxiliary Parameters
Code
Parameter Name
Setting Range
Default Unit
Control Mode
Attribute
V/F SLV
PM
SLV
11-30
Variable carrier frequency
max. limit
2~16
KVA
*a
KHz
O
X
X
11-31
Variable carrier frequency min.
limit
2~16
KVA
*a
KHz
O
X
X
11-32
Variable carrier frequency
proportional gain
00~99
00
-
O
X
X
11-33
Rise Amount of DC Voltage
Filter
0.1~10.0
0.1
Vdc
O
X
X
*1 *7
11-34
Fall Amount of DC Voltage
Filter
0.1~10.0
5.0
Vdc
O
X
X
*1 *7
11-35
Dead band Level of DC
Voltage Filter
0.0~99.0
10.0
Vdc
O
X
X
*1 *7
11-36
Frequency Gain of OV
Prevention
0.000~1.000
0.050
-
O
X
X
*1 *7
11-37
Frequency Limit of OV
Prevention
0.00~400.00
5.00
Hz
O
X
X
*7
11-38
Deceleration Start Voltage of
OV Prevention
200V: 200~400V
400V: 400~800V
200V:
300
400V:
700
V
O
X
X
*7
11-39
Deceleration Stop Voltage of
OV Prevention
200V: 300~400V
400V: 600~800V
220V:
350
440V:
750
V
O
X
X
*7
11-40 OV Prevention Selection
0: Disable
1: OV Prevention Mode 1
2: OV Prevention Mode 2
3: OV Prevention Mode 3
0
-
O
X
X
*7
11-41
Detecting the disappearance
of reference frequency
selection
0: Deceleration to stop when
reference frequency disappears
0
-
O
O
O
1: Operation is set by 11-42 when
reference frequency disappears
11-42
Disappearance level of
reference frequency
0.0~100.0
80.0
%
O
O
O
11-43 Hold frequency at start
0.0~400.0
0.0
Hz
O
O
O
11-44 Frequency hold time at start
0.0~10.0
0.0
s
O
O
O
11-45 Hold frequency at stop
0.0~400.0
0.0
Hz
O
O
O
11-46 Frequency hold time at stop
0.0~10.0
0.0
s
O
O
O
11-47 KEB Deceleration time
0.0~25.5
0.0
s
O
X
X
*1
11-48 KEB Detection level
380~420
400
V
O
X
X
11-49
~
11-50
Reserved
11-51
Braking selection of zero
speed
0: Disable
0
-
O
X
X
1: Enable
11-52
~
11-53
Reserved
11-54
Accumulate energy
initialisation
0: Do not clear cumulative energy
0
-
O
O
O
*1
1: Clear cumulative energy
11-55 STOP Key selection
0: Stop key is disabled when the
operation command is not
provided by keypad.
1
-
O
O
O