Group 24 Pump Control Function Parameters
Code
Parameter Name
Setting Range
Default Unit
Control Mode
Attribute
V/F SLV
PM
SLV
24-00
Selection of pump control
function
0: Function of 1 to 8 pump card is
disabled
0
-
O
O
O
1: Fixed modes of inverter pump:
first on and last off; then stop all.
2: Fixed modes of inverter pump:
only stop inverter pump.
3: Fixed modes of inverter pump:
first on and first off; then stop all.
4: Cycle modes of inverter pump:
first on and first off; then stop all.
5: Cycle modes of inverter pump:
only stop inverter pump.
6: 1 to 3 relay of cycle modes of
inverter pump: first on and first
off; then stop all
24-01 Selection of relay 2-4 function
xxx0b: Reserved
0000b
O
O
O
xxx1b: Reserved
xx0xb: Relay 2 disable
xx1xb: Relay 2 enable
x0xxb: Relay 3 disable
x1xxb: Relay 3 enable
0xxxb: Relay 4 disable
1xxxb: Relay 4 enable
24-02 Selection of relay 5-8 function
xxx0b: Relay 5 disable
0000b
O
O
O
xxx1b: Relay 5 enable
xx0xb: Relay 6 disable
xx1xb: Relay 6 enable
x0xxb: Relay 7 disable
x1xxb: Relay 7 enable
0xxxb: Relay 8 disable
1xxxb: Relay 8 enable
24-03
Duration of upper limit
frequency
1.0~600.0
300.0
S
O
O
O
*1
24-04
Duration of lower limit
frequency
1.0~600.0
300.0
S
O
O
O
*1
24-05
Switching time of magnetic
contactor
0.1~20.0
1.00
S
O
O
O
*1
24-06 Allowable bias of pump switch 0.0~20.0
0.0
%
O
O
O
*1
24-07
Pump control source
selection
0: 1 to 8 pump card
0
O
O
O
1: Control cable
24-08 Relay swap time
0~240
0
hour
24-09 Frequency/ Target Switch
0: Disable
1: Enable
0
O
O
O
*7
24-10
Stop Mode Selection on
Mode 6/7/9
0: Disable
1: Enable
0
O
O
O
*7
24-11 High Pressure Limit Level
0~10000
500
-
O
O
O
*7
24-12
Delay Time of High Pressure
Warning
0.0 ~ 600.0
10.0 Sec
O
O
O
*7
24-13
Delay Time of High Pressure
Error
0.0 ~ 600.0
20.0 Sec
O
O
O
*7
24-14 Low Pressure Limit Level
0~10000
0
-
O
O
O
*7
24-15
Delay Time of Low Pressure
Warning
0.0 ~ 600.0
0.0
Sec
O
O
O
*7