![CARLO GAVAZZI VariFlex3 RVFFA3400400F Скачать руководство пользователя страница 48](http://html1.mh-extra.com/html/carlo-gavazzi/variflex3-rvffa3400400f/variflex3-rvffa3400400f_quick-start-manual_2558654048.webp)
Motor Controllers AC Variable Frequency Drives
Type Variflex
3
RVFF
Specifications are subjected to change without notice.
47
Group 11 Auxiliary Parameters
Code
Parameter Name
Setting Range
Default Unit
Control Mode
Attribute
V/F SLV
PM
SLV
11-00 Motor direction lock selection
0: Allow forward and reverse
rotation
1
-
O
O
O
1: Only allow forward rotation
2: Only allow reverse rotation
11-01 Carrier frequency
0: Carrier output frequency tuning
Inverter
KVA
*a
-
O
O
X
1: Reserved
2~16: 2~16KHz
11-02 Soft PWM function selection
0: Disable
1
*
b
-
O
O
O
1: Soft PWM Function 1
2: Soft PWM Function 2
11-03
Automatic carrier lowering
selection
0: Disable
0
-
O
X
X
1: Enable
11-04
S-curve time setting at the
start of acceleration
0.00~2.50
0.20
s
O
O
O
11-05
S-curve time setting at the
end of acceleration
0.00~2.50
0.20
s
O
O
O
11-06
S-curve time setting at the
start of deceleration
0.00~2.50
0.20
s
O
O
O
11-07
S-curve time setting at the
end of deceleration
0.00~2.50
0.20
s
O
O
O
11-08 Jump frequency 1
0.0~400.0 (according to 01-02)
0.0
Hz
O
O
O
11-09 Jump frequency 2
0.0~400.0 (according to 01-02)
0.0
Hz
O
O
O
11-10 Jump frequency 3
0.0~400.0 (according to 01-02)
0.0
Hz
O
O
O
11-11 Jump frequency width
0.0~25.5
1.0
Hz
O
O
O
11-12 Manual energy saving gain
0~100
80
%
O
X
X
11-13 Auto back time
0~120
60
S
O
O
O
11-14
~
11-17
Reserved
11-18
Manual energy saving
frequency
0.0~400.00
0.00
Hz
O
X
X
11-19
Automatic energy saving
function
0: Automatic energy saving is
disabled
0
-
O
X
X
1: Automatic energy saving is
enabled
11-20
Filter time of automatic energy
saving
0~200
140
ms
O
X
X
11-21
Voltage upper limit of energy
saving tuning
0~100
100
%
O
X
X
11-22
Adjustment time of automatic
energy saving
0~5000
20
ms
O
X
X
*1
11-23
Detection level of automatic
energy saving
0~100
10
%
O
X
X
11-24
Coefficient of automatic
energy saving
0.00~655.34
KVA
*a
-
O
X
X
11-25
~
11-27
Reserved
11-28
Frequency Gain of
Overvoltage Prevention 2
1~200
100
%
O
X
X
11-29 Auto de-rating selection
0: Disable
0
-
O
X
X
1: Enable
Содержание VariFlex3 RVFFA3400400F