Motor Controllers AC Variable Frequency Drives
Type Variflex
3
RVFF
Specifications are subjected to change without notice.
44
Group 09 Communication Parameters
Code
Parameter Name
Setting Range
Default Unit
Control Mode
Attribute
V/F SLV
PM
SLV
09-00
INV communication station
address
1~31
1
-
O
O
O
*2
09-01
Communication mode
selection
0: MODBUS
0
-
O
O
O
1: BACNET
2: METASYS
3: PUMP in parallel connection
4: PROFIBUS
09-02 Baud rate setting (bps)
0:1200
3
-
O
O
O
*2
1:2400
2:4800
3:9600
4:19200
5:38400
09-03 Stop bit selection
0:1 Stop bit
0
-
O
O
O
*2
1: 2 Stop bit
09-04 Parity selection
0: No parity
0
-
O
O
O
*2
1: Even bit
2: Odd bit
09-05 Data bit selection
0: 8 data bits
0
-
O
O
O
1: 7 data bits
09-06
Communication error
detection time
0.0~25.5
0.0
S
O
O
O
09-07 Fault stop selection
0: Deceleration to stop based on
deceleration time 1 when
communication fault occurs.
3
-
O
O
O
1: Coast to stop when
communication fault occurs.
2: Deceleration to stop based on
deceleration time 2 when
communication fault occurs.
3: Keep operating when
communication fault occurs.
09-08 Comm. fault tolerance count
1~20
1
-
O
O
O
09-09 Waiting time
5~65
5
ms
O
O
O
09-10 Device instance number
1~254
0
-
O
O
O
Group 10 PID Parameters
Code
Parameter Name
Setting Range
Default Unit
Control Mode
Attribute
V/F SLV
PM
SLV
10-00
PID target value source
setting
0: Keypad
(for PUMP or HVAC mode)
1
-
O
O
O
*6
1: AI1
2: AI2
3: Reserved
4:10-02
5: Reserved
6: Frequency command (00-05)
7: Multi-speed frequency command