![CARLO GAVAZZI VariFlex3 RVFFA3400400F Скачать руководство пользователя страница 46](http://html1.mh-extra.com/html/carlo-gavazzi/variflex3-rvffa3400400f/variflex3-rvffa3400400f_quick-start-manual_2558654046.webp)
Motor Controllers AC Variable Frequency Drives
Type Variflex
3
RVFF
Specifications are subjected to change without notice.
45
Group 10 PID Parameters
Code
Parameter Name
Setting Range
Default Unit
Control Mode
Attribute
V/F SLV
PM
SLV
10-01
PID feedback value source
setting
1:AI1
2
-
O
O
O
*6
2:AI2
3: Reserved
4: AI1
– AI2 given
10-02 PID Target value
0.0~100.0
0.0
%
O
O
O
10-03 PID Control mode
xxx0b: PID Disable
0000b
-
O
O
O
xxx1b: PID Enable
xx0xb: PID Positive characteristic
xx1xb: PID Negative characteristic
x0xxb: PID Error value of D control
x1xxb: PID Feedback value of D
control
0xxxb: PID Output
1xxxb: PID Target value
10-04 Feedback gain
0.01~10.00
1.00
-
O
O
O
*1
10-05 Proportional gain (P)
0.00~10.00
3.00
-
O
O
O
*1
10-06 Integral time (I)
0.00~100.00
0.50
s
O
O
O
*1
10-07 Differential time (D)
0.00~10.00
0.00
s
O
O
O
*1
10-08
Reserved
10-09 PID Bias voltage
-100.0~100.0
0
%
O
O
O
*1
10-10 PID primary delay time
0.00~10.00
0.00
s
O
O
O
*1
10-11
PID feedback loss detection
selection
0: Disable
0
-
O
O
O
1: Alarm
2: Fault
10-12
PID feedback loss detection
Level
0~100
0
%
O
O
O
10-13
PID feedback loss detection
time
0.0~10.0
1.0
s
O
O
O
10-14 PID Integral limit
0.0~100.0
100.0
%
O
O
O
*1
10-15 /
10-16
Reserved
10-17 Start frequency of PID sleep
0.00~400.00
30.00
Hz
O
O
O
10-18 Delay time of PID sleep
0.0~255.5
0.0
s
O
O
O
10-19 Frequency of PID waking up
0.00~180.00
0.00
Hz
O
O
O
10-20 Delay time of PID waking up
0.0~255.5
0.0
s
O
O
O
10-21
Reserved
10-22 Start level of PID enable
0.00 ~ 400.00
0.00
Hz
O
O
O
*7
10-23 PID Limit
0.00~100.0
100.0
%
O
O
O
*1
10-24 PID Output gain
0.0~25.0
1.0
-
O
O
O
10-25 PID Reversal output selection
0: No allowing reversal output
0
-
O
O
O
1: Allow reversal output
10-26
PID target acceleration/
deceleration time
0.0~25.5
0.0
s
O
O
O
10-27 PID Feedback display bias
-99.99~99.99
0.00
-
O
O
O
10-28 PID Feedback display gain
0.00~100.00
100.00
-
O
O
O
10-29 PID Sleep selection
0: Disable
1
-
O
O
O
1: Enable
2: Set by DI
10-30 PID target upper limit
0.0 ~ 100.0
100.0
%
O
O
O
10-31 PID target lower limit
0.0 ~ 100.0
0.0
%
O
O
O
10-32 PID switching selection
0: PID1
0
O
O
O
1: PID2
2: Set by DI
Содержание VariFlex3 RVFFA3400400F
Страница 1: ...Quick Start Guide Motor Controllers AC Variable Frequency Drives Type VariFlex3 RVFF...
Страница 99: ......