Motor Controllers AC Variable Frequency Drives
Type Variflex
3
RVFF
Specifications are subjected to change without notice.
43
Group 08 Protection Parameters
Code
Parameter Name
Setting Range
Default Unit
Control Mode
Attribute
V/F SLV
PM
SLV
08-31
~
08-34
Reserved
08-35 Motor overheat selection
0: Disable
0
-
O
O
O
1: Deceleration to stop
2: Coast to stop
08-36 PTC input filter time
0.00~5.00
2.00
S
O
O
O
08-37 Fan control selection
0: On when the inverter is running
0
-
O
O
O
1: Always on
2: On when the heatsink
temperature is high*
08-38 Fan delay time
0~600
60
S
O
O
O
08-39
Motor overheat protection
delay time
1~300
60
S
O
O
O
08-42 PTC Trip Level
0.1~10.0
0.7
V
O
O
O
08-43 PTC Reset Level
0.1~10.0
0.3
V
O
O
O
08-45 PTC Disconnection Detection
0: Disable
0
-
O
O
O
*7
1: Warning
2: Fault
08-46
Over-temperature Protection
Level
0~254°C
0
°
C
O
O
O
*7
08-47
Over-temperature Reset
Level
0~254°C
0
°
C
O
O
O
*7
08-48 Fire Mode Selection
0: Disable
1: Enable
0
-
O
O
O
*7
08-49 Fire Mode Digital Input Type
0: Power Loss Reset
1: Terminal Removal Reset
0
-
O
O
O
*7
08-50
Fire Mode Digital Terminal
Status
XXX0b: S6 A contact
XXX1b: S6 B contact
0000b
-
O
O
O
*7
08-51
Fire Mode Motor Speed
Selection
0: Fire Mode Operation
1: PID Frequency Command
2: AI2 Frequency Command
0
-
O
O
O
*7
08-52 Fire Mode Motor Speed
0.00~100.00
100.00 %
O
O
O
*7
08-53
Fire Mode PID Detection
Level
0~100
0
%
O
O
O
*7
08-54
Fire Mode PID Disconnection
Delay
0.0~10.0
1.0
s
O
O
O
*7
08-55
Fire Mode PID Disconnection
Selection
0: Current Speed
1: Fire Mode Speed (08-52)
2: Motor 1 Maximum Frequency
(01-02)
1
-
O
O
O
*7
08-56
Fire Mode AI2 Detection
Level
0.0~100.0
80.0
%
O
O
O
*7
08-57
Fire Mode AI2 Disconnection
Delay
0.0~10.0
1.0
s
O
O
O
*7
08-58
Fire Mode AI2 Disconnection
Selection
0: Current Speed
1: Fire Mode Speed (08-52)
2: Motor 1 Maximum Frequency
(01-02)
1
-
O
O
O
*7
08-59 Fire Mode Motor Direction
0: Forward Direction
1: Reverse Direction
0
-
O
O
O
*7
08-60 Fire Mode Password
00000~65534
0
-
O
O
O
*7
* Models of inverter ratings above RVFFD3403700F do not have this function.