![CARLO GAVAZZI VariFlex3 RVFFA3400400F Скачать руководство пользователя страница 78](http://html1.mh-extra.com/html/carlo-gavazzi/variflex3-rvffa3400400f/variflex3-rvffa3400400f_quick-start-manual_2558654078.webp)
Motor Controllers AC Variable Frequency Drives
Type Variflex
3
RVFF
Specifications are subjected to change without notice.
77
LED
display
Description
Cause
Possible solutions
EF6
(flash)
External
fault (S6)
External fault
(Terminal S6)
Active when 03-05=
25, and Inverter
external fault
selection 08-24=2.
•
Multifunction digital input external fault
active and parameter 08-24 = 2 for
operation to continue.
•
Multi-function input function set
incorrectly.
•
Check wiring
•
Multi-function input function set
incorrectly.
•
Check wiring
EF9
(flash)
error of
forward/rev
ersal
rotation
Forward run and
reverse run are
active within 0.5
sec of each other.
Stop method set by
parameter 07-09.
•
Forward run and reverse run active
(see 2-wire control).
•
Check run command wiring
SE01
Rang
setting
error
Parameter setting
falls outside the
allowed range.
•
Some parameter ranges are
determined by other inverter
parameters which could cause an out
of range warning when the
dependency parameter is adjusted.
For example: 02-00>02-01, 00-12<00-
13 or when 00-07 = 1, 00-05 is the
same with 00-06 or 20-16 <= 20-15.
•
Check parameter setting.
SE02
Digital input
terminal
error
Multi-function input
setting error.
•
Multi-function digital input terminals
(03-00 to 03-05) are set to the same
function (not including ext. fault and
not used.) or
UP/DOWN commands
are not set at the same time (they
must be used together).
UP/DOWN
commands (08 and 09) and ACC/DEC
commands (11) are set at the same
time.
Speed search 1(19
,
maximum frequency) and Speed
search 2 (34
,
from the set
frequency
)
are set at the same time.
•
Check multi-function input
setting.
SE03
V/f curve
error
V/f curve setting
error.
•
V/F curve setting error.
01-02 > 01-12 > 01-06 >01-08;
(Fmax) (Fbase) (Fmid1) (Fmin)
01-16 > 01-24 > 01-20 > 01-22;
(Fmax2) (Fbase2) (Fmid1) (Fmin2)
•
Check V/F parameters