LED display
Description
Cause
Possible solutions
SS1
Safety switch
Inverter safety switches
open.
•
When 08-30 is set to 0: Deceleration
to stop, and digital terminal
switch(58) is turned on.
•
Check digital terminal(58) is
turned on.
EF0
External fault 0 External fault (Modbus)
Modbus communication 0x2501 bit 2=
"1"
•
Reset Modbus
communication 0x2501 bit
2= "1"
EF1
External fault
(S1)
External fault (Terminal S1)
Active when 03-00= 25 or
68, and Inverter external
fault selection 08-24=0 or 1.
•
Multifunction digital input external
fault active.
•
Multi-function input function
set incorrectly.
•
Check wiring
EF2
External fault
(S2)
External fault (Terminal S2)
Active when 03-01= 25 or
68, and Inverter external
fault selection 08-24=0 or 1.
EF3
External fault
(S3)
External fault (Terminal S3)
Active when 03-02= 25 or
68, and Inverter external
fault selection 08-24=0 or 1.
EF4
External fault
(S4)
External fault (Terminal S4)
Active when 03-03= 25 or
68, and Inverter external
fault selection 08-24=0 or 1.
EF5
External fault
(S5)
External fault (Terminal S5)
Active when 03-04= 25 or
68, and Inverter external
fault selection 08-24=0 or 1.
EF6
External fault
(S6)
External fault (Terminal S6)
Active when 03-05= 25 or
68, and Inverter external
fault selection 08-24=0 or 1.
CF07
Motor control
fault
Motor control fault
•
SLV mode is unable to run motor.
•
Perform rotational or
stationary auto-tune
•
Increase minimum output
frequency (01-08)
CF08
Motor control
fault
Motor control fault
•
Start or Run fault in PMSLV mode.
•
Increase the value of 22-10
properly.
•
Re auto-tune (22-21)
•
Check if the load is too heavy
to raise torque output limit.
FU
fuse open
DC bus fuse blown
DC fuse (75HP and above)
open circuit.
•
IGBT damaged.
•
Short circuit output terminals.
•
Check IGBTs
•
Check for short circuit at
inverter output.
•
Replace inverter.