31
Outdoor Sensor connected to Slave boiler 2 (DRH ONLY)
Description
Electrical Connection(s)
Programming Instructions
•
Slave boiler outdoor sensor
configuration
•
When done correctly, the
outdoor temperature will be
shown on the Master boiler
Slave Boiler
1)
Place both toggle switches in
LOCAL
2)
Press
and select Login
3)
Select Advanced Setup
4)
Select
Sensor Configuration
5)
Select
Outdoor temp src
and Press
6)
Select
S5
and Press
Master Boiler
7)
Place both toggle switches in
LOCAL
8)
Press
and select Login
9)
Select Advanced Setup
10)
Select
Lead Lag Config
11)
Select
Lead Lag Outdoor Reset
12)
Select
Outdoor reset enable = Enable and p
ress
13)
Set
Max outdoor temp
(Warm weather shutdown, WWSD)
14)
Set
Min outdoor temp
(Outdoor Design)
15)
Set
Low Water Temp
(Min. Water Temp.)
16)
Set
Outdoor boost maximum off point
(Design Max.)
17)
Select
CH Config
18)
Select
Warm weather shutdown
19)
Select
Warm weather shutdown = Shutdown after demand has ended
and
press
20)
Select
Warm weather shdn setpoint
Содержание DynaMax DMH081
Страница 2: ......
Страница 12: ...7 Figure 5 DynaMax HS Wall Hung Service Clearances Figure 6 DynaMax HS Floor Mount Service Clearances...
Страница 68: ...65 PART 14 EXPLODED VIEW PARTS LIST DYNAMAX HS WALL HUNG...
Страница 69: ...66 DYNAMAX HS FLOOR MOUNT...
Страница 76: ...73 PART 15 ELECTRICAL DIAGRAMS 15 1 DM 80 299 INTERNAL WIRING DIAGRAM...
Страница 77: ...74 15 2 DM 399 800 INTERNAL WIRING DIAGRAM...
Страница 78: ...75...