25
Modulation: System Sensor, Outdoor Reset Operation (Standalone)
NOTE: Outdoor Reset Module (PN: 50022037-001) and outdoor sensor (PN: C7089U1006) required
Description
Electrical Connection(s)
Programming Instructions
•
Boiler operates with variable
setpoint determind by
outdoor reset curve
•
Modulates on system sensor
•
Heat demand is generated
when Remote Operator is
closed.
1)
Connect Remote Operator
2)
Connect System sensor to System/Outdoor contacts
3)
Connect Outdoor Sensor to J3 ECOM connector
4)
Place both toggle switches in
LOCAL
5)
Press
and select Login
6)
Select Advanced Setup
7)
Select
CH Config
8)
Select
Outdoor Reset Config
9)
Select
Outdoor
Reset and Press
and select
Enable
10)
Set
Max outdoor temp
(Warm Weather shutdown, WWSD)
11)
Set
Min outdoor temp
(Outdoor Design)
12)
Set
Low Water temp
(Min. Water Temp.)
13)
Set
Outdoor boost max off point
(Design Max.)
14)
Select
Sensor Configuration
15)
Select
Outdoor temp src
and Press
16)
Select
EnviraCOM
and Press
17)
Select Select
CH Config
(twice)
18)
Select
Modulation sensor = S5
19)
Place right hand toggle switch to
REMOTE
for remote operation (if
required)
Содержание DynaMax DMH081
Страница 2: ......
Страница 12: ...7 Figure 5 DynaMax HS Wall Hung Service Clearances Figure 6 DynaMax HS Floor Mount Service Clearances...
Страница 68: ...65 PART 14 EXPLODED VIEW PARTS LIST DYNAMAX HS WALL HUNG...
Страница 69: ...66 DYNAMAX HS FLOOR MOUNT...
Страница 76: ...73 PART 15 ELECTRICAL DIAGRAMS 15 1 DM 80 299 INTERNAL WIRING DIAGRAM...
Страница 77: ...74 15 2 DM 399 800 INTERNAL WIRING DIAGRAM...
Страница 78: ...75...