Installing the boiler
Logano G225/Logano plus GB225 - We reserve the right to make any changes due to technical modifications.
39
6.1.2
Flue pipe sealing collar for positive pressure flue (pressure at boiler outlet > 0 mbar)
The overpressure-tight flue pipe sealing collar
(accessories, part no. 535 4404) must be fitted.
V
Slide the flue pipe sealing collar [3] and two jubilee
clips [2] over the flue pipe [4].
V
Push flue pipe [4] and flue pipe sealing collar [3] onto
the boiler flue outlet [1].
V
Tighten jubilee clips [2].
Fig. 54 Making the flue pipe sealing collar
1
Flue outlet
2
Jubilee clip
3
Flue pipe sealing collar
4
Flue pipe
6.2
Fitting the water connections
6.2.1
Connecting the central heating flow and
return
V
Connect central heating return to connection RK.
V
Connect the central heating flow to connection VK.
Fig. 55 Connecting the central heating flow and return
Key to fig. 55 - 58:
VSL: Flow safety line
VK: Boiler flow
RK: Boiler return
VS: DHW cylinder flow
RS: DHW cylinder return
EL:
Drain
6 720 615 876-54.1RS
2
2
4
3
3
1
Caution: Risk of system damage from
leaking connections.
V
Fit the connecting pipes to the boiler in
such a way that they are not under stress.
Caution: Risk of system damage due to lack
of water.
The boiler requires a minimum pressure
switch to protect it against lack of water. You
can obtain this as an accessory.
V
Observe the installation instructions for
the accessory.
We recommend fitting a dirt filter (option) to
the central heating return to prevent
contamination of the boiler by the water.
6 720 615 876-55.1RS
VK
RK