3.1
Specifications for boiler without burner
Select a suitable burner for this boiler using the
information in this section.
Fig. 2
Dimensions and connections (dimensions in mm)
Connections (for dimensions see the following tables):
VK
= Boiler flow
VS
= DHW cylinder flow
RK
= Boiler return
RS
= DHW return
EL
= Drain (connection for boiler fill and drain valve)
VSL = Safety flow pipe (connection for an on-site air vent valve)
Boiler rating
52
64
78
95
Boiler sections
Number
4
5
6
7
Rated output
kW
40 – 52
48 – 64
59 – 78
71 – 95
Combustion output
kW
44,0 – 56,6
51,5 – 69,8
63,3 – 85,1
76,0 – 103,2
Boiler water content
I
approx. 61
approx. 73
approx. 85
approx. 97
Gas content
I
68,8
85,1
101,4
117,7
Flue gas temperature
1
°C
160 – 198
Flue gas mass flow, oil
Partial load at 60 %
kg/s
–
–
0,021
0,026
Flue gas mass flow, oil Full load
2
kg/s
0,018 – 0,024
0,022 – 0,030
0,027 – 0,036
0,032 – 0,044
CO
2
content, oil
%
13
Flue gas mass flow rate, gas
Partial load at 60 %
kg/s
–
–
0,021
0,026
Flue gas mass flow rate, gas
Full load
3
kg/s
0,018 – 0,024
0,022 – 0,030
0,027 – 0,36
0,032 – 0,044
CO
2
contents, gas
%
10
Required draught
Pa
0
Tab. 1
Specification for boiler without burner
1
Flue gas temperature acc. to EN 303.
2
Full load details relate to the upper and lower rated output range.
3
Safety limit (high limit safety cut-out). Max. possible flow temperature = high limit (STB).
Max. possible flow temperature = high limit (STB)
–
18 K
Example: Safety limit (STB) = 100 °C, max. possible flow temperature = 100
–
18 = 82 °C.
Содержание Logano G215 WS
Страница 58: ...Index 13 Logano G215 WS We reserve the right to make any changes due to technical modifications 58...
Страница 59: ...Notes Logano G215 WS We reserve the right to make any changes due to technical modifications 59...
Страница 60: ...Notes Logano G215 WS We reserve the right to make any changes due to technical modifications 60...
Страница 61: ...Notes Logano G215 WS We reserve the right to make any changes due to technical modifications 61...