Commissioning the heating system
9
Logano G215 WS - We reserve the right to make any changes due to technical modifications.
44
9.4.1 Removing hot gas baffle plates
You can remove the hot gas baffles in pairs to raise the
flue gas temperature.
z
Open the burner door; for this purpose, remove the
two lateral hexagon bolts.
z
Remove the hot gas baffles towards the front.
z
Close the burner door with both hexagon bolts.
Tighten the hexagon bolts evenly to properly seal the
burner door.
z
Re-check the flue gas temperature.
9.4.2 Removing the hot gas check plate
You can remove the hot gas check plate to raise the flue
gas temperature even higher if it is still too low after
removing the hot gas baffle plates.
z
Open the burner door; for this purpose, remove the
two lateral hexagon bolts.
z
Remove the hot gas check plate; for this purpose
remove the screw.
z
Re-check the flue gas temperature.
9.5
Checking the high limit safety cut-out (STB)
The high limit safety cut-out interrupts the energy supply
when the maximum permissible flow temperature is
exceeded. To enable the boiler to be reset and re-
started, the fault must be removed and the system must
have dropped below the limit.
z
Check the high limit safety cut-out function
(
Î
control device service instructions).
Fig. 66 Removing hot gas baffle plates (example: 2. hot gas
flue)
Fig. 67 Removing the hot gas check plate
Содержание Logano G215 WS
Страница 58: ...Index 13 Logano G215 WS We reserve the right to make any changes due to technical modifications 58...
Страница 59: ...Notes Logano G215 WS We reserve the right to make any changes due to technical modifications 59...
Страница 60: ...Notes Logano G215 WS We reserve the right to make any changes due to technical modifications 60...
Страница 61: ...Notes Logano G215 WS We reserve the right to make any changes due to technical modifications 61...