Commissioning the heating system
9
Logano G215 WS - We reserve the right to make any changes due to technical modifications.
43
9.3
Commissioning the control device and the burner
To continue the commissioning procedure, follow the
steps for commissioning the burner. Refer to the
Î
burner documentation.
Start up the heating system using the control device
ON/OFF switch. The burner starts if a heat demand is
present or if you switch the control device to manual
(
Î
control device service instructions).
z
Set the desired temperature on the boiler water
thermostat.
z
Select "Manual" mode
.
z
Switch the ON/OFF switch on (position "I").
9.4
Raising the flue gas temperature
For the set flue gas temperature for the boiler, see the
Specifications (
Î
Section 3, page 7)
You may raise the flue gas temperature using one or
more of the measures listed below if you notice during
testing that the flue gas temperature is too low for the
type of chimney used (risk of condensation):
–
Remove hot gas baffle plates
–
Remove the hot gas check plate
z
Shut down the heating system (
Î
Section 10.1,
page 47).
Fig. 65 Starting up the control device (for example
Logamatic 2000)
1
Boiler water thermostat
2
ON/OFF switch
I 0
2
1
WARNING!
RISK OF EXPLOSION
through escaping gas.
z
Close the main shut-off valve if gas
pipes need to be pulled off the gas
burner to open the burner door. Route
the remaining escaping gas outdoors.
CAUTION!
RISK OF BURNING
through touching hot boiler parts.
z
Wear appropriate protective gloves or
use pliers.
Содержание Logano G215 WS
Страница 58: ...Index 13 Logano G215 WS We reserve the right to make any changes due to technical modifications 58...
Страница 59: ...Notes Logano G215 WS We reserve the right to make any changes due to technical modifications 59...
Страница 60: ...Notes Logano G215 WS We reserve the right to make any changes due to technical modifications 60...
Страница 61: ...Notes Logano G215 WS We reserve the right to make any changes due to technical modifications 61...