Assembling the boiler block
7
Logano G215 WS - We reserve the right to make any changes due to technical modifications.
20
7.1.6 Boiler section alignment
z
Right the part assembled block comprising two boiler
sections.
z
Position a flat board underneath the centre section
so that the boiler block is slightly tilted for the next
stages of assembly.
7.1.7 Joining the boiler sections at the upper and
lower boiler hubs using nipples
CAUTION!
RISK OF INJURY
through inadequately secured boiler
sections.
z
Secure the boiler block section against
tipping.
Fig. 11 Righting the part assembled block
1
Flat board
2
Centre section
1
2
CAUTION!
BOILER DAMAGE
through an unsuitable compression tool.
z
Use only the Buderus compression tool
size 1.2.
Fig. 12 Making the pull rod threaded connection
1
Pull rod threaded connection (incorrectly joined)
2
Pull rod threaded connection (correctly joined)
1
2
CAUTION!
DAMAGE TO COMPRESSION TOOL
The compression tool may be damaged or
destroyed if you compress pull rods with
loose threaded connections.
z
Check the threaded connection of the
pull rods after every compression, and
tighten, if required.
The pull rod is correctly positioned if it
is fully inserted and no thread is
showing.
z
Keep the thread of the compression
tool clean. Dirty threads can damage
the compression tool during
compression.
Содержание Logano G215 WS
Страница 58: ...Index 13 Logano G215 WS We reserve the right to make any changes due to technical modifications 58...
Страница 59: ...Notes Logano G215 WS We reserve the right to make any changes due to technical modifications 59...
Страница 60: ...Notes Logano G215 WS We reserve the right to make any changes due to technical modifications 60...
Страница 61: ...Notes Logano G215 WS We reserve the right to make any changes due to technical modifications 61...