Specifications
3
Logano G215 WS - We reserve the right to make any changes due to technical modifications.
12
3.3.6 Conditions for hydraulic system and water quality
Operating conditions
Notes
–
detailed requirements
Operating pressure
(overpressure)
0,5 – 4,0 bar
Permissible site test pressure
1,0 – 5,2 bar
Protection against over-
temperatures via TR
thermostat
50 – 90 °C
Protection against over-
temperatures via STB high
limit safety cut-out
100 – 120 °C
Some control devices adjustable on site from 100 to 120 °C.
Water quality
–
Only use drinking water to fill and top up the boiler. We recommend a pH value
of 8.2 – 9.5.
Tab. 7
Hydraulic system and water quality