Specifications
3
Logano G215 WS - We reserve the right to make any changes due to technical modifications.
8
3.2
Declaration of conformity
Hot gas resistance
mbar
0,30 – 0,42
0,16 – 0,35
0,25 – 0,46
0,35 – 0,71
Permissible flow temperature
3
°C
120
Permissible operating pressure
bar
4
Maximum time constant of thermostat and
high limit safety cut-out (STB)
s
40
Boiler rating
52
64
78
95
Tab. 1
Specification for boiler without burner
1
Flue gas temperature acc. to EN 303.
2
Full load details relate to the upper and lower rated output range.
3
Safety limit (high limit safety cut-out). Max. possible flow temperature = high limit (STB).
Max. possible flow temperature = high limit (STB)
–
18 K
Example: Safety limit (STB) = 100 °C, max. possible flow temperature = 100
–
18 = 82 °C.
Boiler rating
52
64
78
95
Overall boiler length (L)
mm
787
907
1027
1147
Length of boiler block (L
K
)
mm
680
800
920
1040
Transport dimensions of a single boiler
section (width/height/depth)
mm
–
460 / 820 / 150
Transport dimensions of boiler block
(width/height/depth)
mm
460 / 820 / Länge L
K
Length of combustion chamber
mm
548
668
788
908
Diameter of combustion chamber
mm
337
Depth of burner door
mm
95
Blast tube diameter (D
B
)
mm
112
112
112
130
Circular hole diameter (D
L
)
mm
150
150
150
170
Section feet clearance (F
L
)
mm
455
575
695
815
Net weight
1
kg
227
272
317
362
Tab. 2
Dimensions, weight and other information for boilers without burners
1
Weight incl. packaging approx. 6 - 8% higher.
The design and operation of this product
conforms to European Directives and the
supplementary national requirements. Its
conformity is confirmed by the CE marking.
You can view the Declaration of Conformity
on the internet at www.buderus.de/konfo or
request a copy from your local Buderus
office.
Содержание Logano G215 WS
Страница 58: ...Index 13 Logano G215 WS We reserve the right to make any changes due to technical modifications 58...
Страница 59: ...Notes Logano G215 WS We reserve the right to make any changes due to technical modifications 59...
Страница 60: ...Notes Logano G215 WS We reserve the right to make any changes due to technical modifications 60...
Страница 61: ...Notes Logano G215 WS We reserve the right to make any changes due to technical modifications 61...