Servicing
14
81
We reserve the right to make any changes due to technical modifications!
Installation and Servicing Instructions Logamax plus GB142-24/30/45/60 • Version 12/2004
Buderus Hydronic Systems • http://www.buderus.net
z
Disassemble the supply and return sensors
(see fig. 124, pos. 1 and 2).
z
Dismantle the safety sensor (see fig. 125, pos. 1).
z
Disconnect the hot surface ignitor and ionization
electrode plugs.
z
Loosen the fastening screws (see fig. 126, pos. 1).
z
Pull the earth cable from the hot surface ignitor
(see fig. 126, pos. 2).
z
Dismantle the mounting plate (see fig. 126, pos. 3).
Fig. 124 Replacing the supply/return sensors
1
2
WARNING
To prevent mix-ups, the supply sensor is
marked by a red sleeve on the side of the
cable harness.
Fig. 125 Dismantling the safety sensor
1
Fig. 126 Replacing the hot surface ignitor