BC10 basic controller
10
z
Press the "Chimney Sweep"
or "Reset"
buttons
to set the pump post-purge period. The pump post-
purge period can be set from 5 – 60 minutes (
)
-
)
) or to 24 hours (
)G
).
z
Press the "Service"
button to confirm the setting.
/
NOTICE
On thermostat only systems a 5 to 10 minute
post-purge setting is recommended to purge
heat from the appliance.