Regulations and guidelines
2
7
We reserve the right to make any changes due to technical modifications!
Installation and Servicing Instructions Logamax plus GB142-24/30/45/60 • Version 12/2004
Buderus Hydronic Systems • http://www.buderus.net
2
Regulations and guidelines
The installation must be conform to the requirements of
the authority having jurisdiction or, in the absence of
such requirements, to the latest edition of the National
Fuel Gas Code, ANSI Z223.1. In Canada, installation
must be in accordance with the requirements of
CAN/CGA B149.1 or 2 Installation Code for Gas Burning
Appliances and Equipment.
Where required by the authority having jurisdiction, the
installation must conform to the Standard for Controls
and Safety Devices for Automatically Fired Boilers,
ANSI/ASME CSD-1.
Install CO detectors per local regulations. Appliance
requires yearly maintenance, see maintenance section
see chapter 13 "Maintenance", page 46
Operating Limits of the appliance:
Max. appliance temperature:
220 °F (105 °C)
Max. operating pressure:
44
psi
(3 bar)
The hot water distribution system must comply with all
applicable codes and regulations. When replacing an
existing appliance, it is important to check the condition
of the entire hot water distribution system to ensure safe
operation.