Servicing
14
55
We reserve the right to make any changes due to technical modifications!
Installation and Servicing Instructions Logamax plus GB142-24/30/45/60 • Version 12/2004
Buderus Hydronic Systems • http://www.buderus.net
z
Fit the casing.
z
Connect the heating system to the power supply,
insert the main fuse or switch on the circuit breaker.
z
Set the main switch on the BC10 to "1" (On).
14.9 Checking the supply/return/safety
sensors cable
z
Check all plug and socket connections of the sensors
and the UBA3.
A plug that has not been inserted correctly may be
the cause for a fault message.
Then start the appliance by pressing "Reset"
.
z
Disconnect the heating system from the power
supply, remove the main fuse or switch off the circuit
breaker.
z
Set the main switch on the BC10 to "0" (Off).
z
Remove the casing.
z
Loosen the fastening screw of the UBA3 (see fig. 57,
pos. 1).
z
Remove the UBA3 by pulling it forward as indicated
by the arrow (see fig. 57, pos. 2).
z
Disconnect the plug and socket connection of the
cable for the sensor.
Fig. 56
Replacing the safety sensor
1
NOTICE!
Fill and purge the Logamax plus GB142 as
required. See page 28.
Fig. 57
Dismantling the UBA3
1
2
WARNING!
Avoid damage: do not push the measuring
pin of the volt-ohm-multiammeter too
deeply into the socket.