Servicing
14
53
We reserve the right to make any changes due to technical modifications!
Installation and Servicing Instructions Logamax plus GB142-24/30/45/60 • Version 12/2004
Buderus Hydronic Systems • http://www.buderus.net
z
Remove the air suction tube (see fig. 52, pos. 1).
z
Remove the fan unit fastening screw (see fig. 52,
pos. 2).
z
Remove the fan unit by swinging it to the right
(see fig. 52, pos. 3).
z
Install the new fan unit.
z
Install the fastening screw, air suction tube and both
plugs.
z
Fit the casing.
z
Connect the heating system to the power supply,
insert the main fuse or switch on the circuit breaker.
z
Set the main switch on the BC10 to "1" (On).
14.7 Checking the supply/return/safety/
hot-water temperature sensors
z
Disconnect the heating system from the power
supply, remove the main fuse or switch off the circuit
breaker.
z
Set the main switch on the BC10 to "0" (Off).
z
Remove the casing.
z
Disconnect the plug and socket connection of the
cable for the sensor concerned.
z
Test the resistance of the sensor concerned.
Supply sensor see fig. 53, pos. 1.
Return sensor see fig. 53, pos. 2.
Safety sensor see fig. 54, pos. 1.
z
Measure the temperature near the sensor using a
seconds thermometer.
z
Compare the values measured to the values in
table 13 on the next page. If the values differ, the
sensor is broken.
z
Reconnect the plug and socket connection if the
sensor is OK.
z
Fit the casing.
z
Connect the heating system to the power supply,
insert the main fuse or switch on the circuit breaker.
z
Set the main switch on the BC10 to "1" (On).
Fig. 52
Dismantling the fan unit
1
2
3
Fig. 53
Checking the supply/return sensors
V
1
2
WARNING!
Avoid damage: do not push the measuring
pin of the volt-ohm-multiammeter too
deeply into the socket.
Fig. 54
Checking the safety sensor
1