Start-up procedure
9
31
We reserve the right to make any changes due to technical modifications!
Installation and Servicing Instructions Logamax plus GB142-24/30/45/60 • Version 12/2004
Buderus Hydronic Systems • http://www.buderus.net
z
Briefly press on the control panel cover to open it.
z
Switch on the heating system by setting the main
switch to position "1" (see chapter 10 "BC10 basic
controller", page 36).
z
Press the "Chimney Sweep"
button and hold it (for
approx. two seconds) until the display shows a
decimal point.
z
Measure the gas connection pressure as soon as the
"Burner" LED lights and enter this value in the start-
up report.
The inlet gas pressure must be:
– for natural gas - min. 6.5 – 9.6 inch W.C.
(17 – 25 mbar), nominal supply pressure
7.7 inch W.C. (20 mbar).
– for LPG - min. 8.0 inch W.C. (19.9 mbar), max.
13.0 inch W.C. (32.3 mbar), nominal supply pressure
11.0 inch W.C. (27.3 mbar)
z
Repeatedly press the "Service"
button until the
temperature indication is displayed.
z
Press the "Chimney Sweep"
button to end the
measurement procedure.
z
Close the gas shut-off valve.
z
Remove the connection hose again and tighten the
screw plug on the testing nipple.
z
Open the gas shut-off valve again.
9.8
Checking and adjusting the gas/air
ratio
z
Switch off the heating system using the main switch.
Fig. 29
Opening the control panel
CAUTION
– Contact the relevant gas utility company if
the required inlet gas pressure is not
available.
– Install a gas pressure regulator before the
gas burner fitting if the supply pressure is
too high.