14
14.5 Checking the fan unit; Tacho cable
z
Remove the casing.
z
Disconnect the heating system from the power
supply, remove the main fuse or switch off the circuit
breaker.
z
Set the main switch on the BC10 to "0" (Off).
z
Dismantle the tacho cable plug.
z
Loosen the fastening screw of the UBA3 (see fig. 48,
pos. 1).
z
Remove the UBA3 by pulling it forward as indicated
by the arrow (see fig. 48, pos. 2).
z
Test the tacho cable to make sure that there is no
short circuit in it and that it is not broken (see fig. 50).
z
Assemble the tacho cable plug.
z
Re-assemble the UBA3 in reverse order of
disassembly.
z
Fit the casing.
z
Connect the heating system to the power supply,
insert the main fuse or switch on the circuit breaker.
z
Set the main switch on the BC10 to "1" (On).
14.6 Replacing the fan unit
z
Disconnect the heating system from the power
supply, remove the main fuse or switch off the circuit
breaker.
z
Set the main switch on the BC10 to "0" (Off).
z
Remove the casing.
z
Remove both cable plugs from the fan unit
(see fig. 51, pos. 1).
Fig. 50
UBA3 installation base
Pin
1
28 55
Pin
81
Pin
16
Pin
1
KIM
16-pole connector
81-pole connector
WARNING!
Avoid damage: do not push the measuring
pin of the volt-ohm-multiammeter too
deeply into the socket.
Fig. 51
Disconnect the cable plug from the fan unit
1
NOTICE!
Follow the installation instructions for 120V
fan units!