20
We reserve the right to make any changes due to technical modifications!
Installation and Servicing Instructions Logamax plus GB142-24/30/45/60 • Version 12/2004
Buderus Hydronic Systems • http://www.buderus.net
Installation
6
Below are approved examples of vertical and
horizontal venting installation
Fig. 15
Vertical venting system (sealed combustion)
INTAKE
EXHAUST
10"- 0" MIN
(250 mm - 0 mm MIN)
12" (300 mm) OVER MAXIMUM
SNOW LEVEL OR 24" (600 mm)
WHICHEVER IS
GREATER
3" (80 mm)
3" (80 mm)
1
Fig. 16
Vertical venting system (room air only)
INTAKE
EXHAUST
10"- 0" MIN
(250 mm - 0 mm MIN)
12" (300 mm) OVER MAXIMUM
SNOW LEVEL OR 24" (600 mm)
WHICHEVER IS
GREATER
3" (80 mm)
Fig. 17
Vertical parallel venting system (sealed combustion)
INTAKE
EXHAUST
10"- 0" MIN
(250 mm - 0 mm MIN)
12" (300 mm) OVER MAXIMUM
SNOW LEVEL OR 24" (600 mm)
WHICHEVER IS
GREATER
3" (80 mm)
3" (80 mm)