6.5
Combustion Air and Ventilation
Openings
CAUTION:
APPLIANCE DAMAGE AND OPERA-
TIONAL FAILURES !
Due to insufficient or lacking openings for
combustion air and/or ventilation of the
appliance room.
Provisions for combustion air and ventila-
tion are always required, regardless
whether the combustion air is taken from
the outside (sealed combustion) or inside
(room air for combustion).
Insufficient ventilation of the appliance
room can lead to high air temperatures.
This can result in appliance damage.
– Make sure that intake and exhaust
openings are sufficiently sized and no
reduction or closure of openings takes
place.
– When the problem is not resolved, do
not operate the appliance.
– Please note these restrictions and its
dangers to the operator of the appliance.
WARNING:
APPLIANCE DAMAGE !
due to contaminated air.
– Appliance must be clear and free from
combustible materials, gasoline and
other flammable vapors and liquids, and
corrosive liquids and vapors.
Never use chlorine and hydrocarbon
containing chemicals (such as spray
chemicals, solution and cleaning
agents, paints, glues etc) in the vicinity
of the appliance.
– Do not store and use these chemicals in
the appliance room.
– Avoid excessive dust formation and
build-up.
NOTICE
When one expects contaminated combus-
tion air (near swimming pools, chemical
cleaning operations and hair salons),
sealed combustion operation is recom-
mended.
DANGER:
FIRE DANGER !
due to flammable materials or liquids.
– Do not store flammable materials and
liquids in the immediate vicinity of the
appliance.