Servicing
14
65
We reserve the right to make any changes due to technical modifications!
Installation and Servicing Instructions Logamax plus GB142-24/30/45/60 • Version 12/2004
Buderus Hydronic Systems • http://www.buderus.net
14.21 Replacing the gas control valve
z
Disconnect the heating system from the power
supply, remove the main fuse or switch off the circuit
breaker.
z
Set the main switch on the BC10 to "0" (Off).
z
Remove the casing.
z
Close the gas shut-off valve (see fig. 80, pos. 1).
z
Remove the cable plug from the gas control valve
(see fig. 81, pos. 1).
z
Remove both cable plugs from the fan unit
(see fig. 82, pos. 1).
Fig. 80
Gas shut-off valve closed (1),
gas shut-off valve open (2)
DANGER
Work on gas pipes and fittings must only
be carried out by a registered service
provider.
Fig. 81
Removing the gas control valve plug
Fig. 82
Disconnect the cable plug from the fan unit
1