Servicing
14
61
We reserve the right to make any changes due to technical modifications!
Installation and Servicing Instructions Logamax plus GB142-24/30/45/60 • Version 12/2004
Buderus Hydronic Systems • http://www.buderus.net
14.16 Checking the ionization electrode;
replace if necessary
z
Disconnect the heating system from the power
supply, remove the main fuse or switch off the circuit
breaker.
z
Set the main switch on the BC10 to "0" (Off).
z
Remove the casing.
z
Disconnect the plug and socket connection of the
cable.
z
Set the volt-ohm-multiammeter to "Resistance
testing".
z
Test the earth connection circuit of the ionization
electrode (see fig. 66). The height of the resistance
value must be infinite.
z
Loosen the fastening screws (see fig. 68, pos. 1).
z
Remove the earth cable (see fig. 68, pos. 2).
z
Remove the mounting plate (see fig. 68, pos. 3).
z
Dismantle the ionization electrode (see fig. 68,
pos. 4).
z
Set the volt-ohm-multiammeter to "Resistance
measurement".
z
Test the resistance of the ionization electrode (see
fig. 69). The resistance must be 0
:
.
z
Do a visual check of the ionization electrode.
z
Check the ionization electrode for contamination,
wear or damage (see fig. 70).
z
Replace the ionization electrode if required.
z
Install a new ionization electrode with a new gasket
and secure the mounting plate with the fastening
screws.
z
Fit the earth cable (see fig. 68, pos. 2).
z
Restore the plug and socket connection.
z
Fit the casing.
z
Connect the heating system to the power supply,
insert the main fuse or switch on the circuit breaker.
z
Set the main switch on the BC10 to "1" (On).
Fig. 68
Replacing the ionization electrode
Fig. 69
Testing the resistance of the ionization electrode
Fig. 70
Checking the ionization electrode