Figure 7-2b Commissioning subprocess
flowchart 1 (V/F control)
Figure 7-2c Commissioning subprocess
flowchart 2 (Vector control)
Go to the total
procedure chart
Set F1-00 to F1-04
according to motor
nameplate
Set V/F curve according
to load type
Set F1-06
to F1-10
according
to motor
parameters
F1-37=3:
Complete
static auto-
tuning
F1-37=2:
Dynamic auto-
tuning
Can the
load be removed
from the shaft
of motor?
NO
YES
Have you obtained
accurate motor
parameters?
NO
YES
Sub-procedure 1
Go to the total
procedure chart
Set F1-06
to F1-10
according
to motor
parameters
F1-37=3:
Complete
static auto-
tuning
F1-37=2:
Dynamic auto-
tuning
Set F1-27,
F1-28 and
F1-34
Can the
load be removed
from the shaft
of motor?
Set F1-00 to
F1-04 according
to motor
nameplate
NO
YES
NO
YES
YES
Sub-procedure 2
Have you obtained
accurate motor
parameters?
With
speed feedback
encoder?
NO
7. BASIC OPERATIONS AND TRIAL RUN