6. PANEL OPERATION
Function
Code
Name
Setting Range
Default
Change
Group F9: Fault and Protection (continued)
F9-17
Frequency upon 3rd
(latest) fault
—
—
•
F9-18
Current upon 3rd
(latest) fault
—
—
•
F9-19
Bus voltage upon 3rd
(latest) fault
—
—
•
F9-20
DI state upon 3rd
(latest) fault
—
—
•
F9-21
DO state upon 3rd
(latest) fault
—
—
•
F9-22
AC drive state upon 3rd
(latest) fault
—
—
•
F9-23
Power-on time upon 3rd
(latest) fault
—
—
•
F9-24
Running time upon 3rd
(latest) fault
—
—
•
F9-27
Frequency upon 2nd fault
—
—
•
F9-28
Current upon 2nd fault
—
—
•
F9-29
Bus voltage upon 2nd fault
—
—
•
F9-30
DI state upon 2nd fault
—
—
•
F9-31
DO state upon 2nd fault
—
—
•
F9-32
AC drive state upon
2nd fault
—
—
•
F9-33
Power-on time upon 2nd fault
—
—
•
F9-34
Running time upon 2nd fault
—
—
•
F9-37
Frequency upon 1st fault
—
—
•
F9-38
Current upon 1st fault
—
—
•
F9-39
Bus voltage upon 1st fault
—
—
•
F9-40
DI state upon 1st fault
—
—
•
F9-41
DO state upon 1st fault
—
—
•
F9-42
AC drive state upon 1st fault
—
—
•
F9-43
Power-on time upon 1st fault
—
—
•
F9-44
Running time upon 1st fault
—
—
•
F9-47
Fault protection action
selection 1
Units position: Motor overload (Err11)
0: Coast to stop
1: Stop according to the stop mode
2: Continue to run
Tens position: Input phase loss (Err12)
Hundreds position: Output phase loss (Err13)
Thousands position: External fault (Err15)
Ten thousands position: Communication fault
(Err16)
00000
✩
F9-48
Fault protection action
selection 2
Units position: Encoder fault (Err20)
0: Coast to stop
Tens position: EEPROM read-write fault (Err21)
0: Coast to stop
1: Stop according to the stop mode
Hundreds position: AC drive overload fault
selection (Err10)
0: Coast to stop
1: De-rated running
Thousands position: Motor overheat (Err45)
Ten thousands position: Accumulative running
time reached (Err26)
00000
✩