![BENSHAW PowerPro RSI-PPVC-0001-4-3-B-IP20-IM Скачать руководство пользователя страница 20](http://html1.mh-extra.com/html/benshaw/powerpro-rsi-ppvc-0001-4-3-b-ip20-im/powerpro-rsi-ppvc-0001-4-3-b-ip20-im_user-manual_2735254020.webp)
benshaw.com
20
3
Table 3-1a Model and technical data (continued)
Item
Specification
Model Number
RSI-PPV
C-0
060-4-3-B-XN0
1-IM
RSI-PPV
C-0
075-4-3-B-XN0
1-IM
RSI-PPV
C-0
10
0-4-3-B-XN0
1-IM
RSI-PPV
C-0
125-4-3-X-XN0
1-IM
RSI-PPV
C-0
150-4-3-X-XN0
1-IM
RSI-PPV
C-0
175-4-3-X-XN0
1-IM
RSI-PPV
C-020
0-4-3-X-XN0
1-IM
RSI-PPV
C-0250-4-3-X-IP0
0-IM
RSI-PPV
C-030
0-4-3-X-IP0
0-IM
RSI-PPV
C-0350-4-3-X-IP0
0-IM
RSI-PPV
C-0375-4-3-X-IP0
0-IM
RSI-PPV
C-040
0-4-3-X-IP0
0-IM
RSI-PPV
C-0450-4-3-X-IP0
0-IM
RSI-PPV
C-050
0-4-3-X-IP0
0-IM
RSI-PPV
C-060
0-4-3-X-IP0
0-IM
Applicable motor
capacity (HP)
60
75
100
125
150
175
200
250
300
350
375
400
450
500
600
Applicable motor
capacity (kW)
45
55
75
90
110
132
160
200
220
250
280
315
355
400
450
Outputs Rated
output
current
(460V)
89.8 110.5 148.0 173.6 207.1 249.6 299.9 371.9 420.2 458.7 512.9 577.0 641.2 715.1 808.8
Outputs
voltage
Three-phase 380 to 480V (proportional to input voltage)
Max.
output
frequency
500 Hz (editable through parameter)
Carrier
frequency
0.8 to 8.0 kHz
0.8 to 6.0 kHz (automatically adjusted according to the load characteristics)
Overload
capacity
150% for 60s (130% for 60s in RSI-PPVC-0600-4-3-X-IP00-IM)
Inputs
Rated input
current (A)
89
106
139
164
196
240
287
365
410
441
495
565
617
687
782
Power
supply
Rated
voltage
and
frequency
AC: Three-phase 380 to 480V, 50/60 Hz
Allowed
voltage
fluctuation
-15% to 10%, 323 to 528 VAC
Allowed
frequency
fluctuation
±5%
Power
capacity
(kVA)
81
97
127
150
179
220
263
334
375
404
453
517
565
629
716
Thermal
design
Heat Loss
(W)
1010 1210 1570 1810 2140 2850 3560 4150 4550 5060 5330 5690 6310 6910 7540
Air flow
(CFM)
122.2 122.2 218.6 287.2 354.2 547
627
638.4 722.5 789.4 882
645
860
860
860