75
6
Function
Code
Name
Setting Range
Default
Change
Group F9: Fault and Protection (continued)
FA-25
PID integral property
Units position: Integral separation
0: Disabled
1: Enabled
Tens position: Whether to stop integral
operation when the PID output
reaches the limit
0: Continue integral operation
1: Stop integral operation
00
✩
FA-26
Detection level of
PID feedback loss
0.0%: No detection
0.1% to 100.0%
0.0%
✩
FA-27
Detection time of
PID feedback loss
0.0s to 20.0s
0.0s
✩
FA-28
Selection of PID
operation at stop
0: Disabled
1: Enabled
0
✩
Group FB: Fixed Length and Count
FB-00
Wobble setting mode
0: Relative to the frequency reference
1: Relative to the max. frequency
0
✩
FB-01
Wobble amplitude
0.0% to 100.0%
0.0%
✩
FB-02
Wobble step
0.0% to 50.0%
0.0%
✩
FB-03
Wobble cycle
0.0s to 3000.0s
10.0s
✩
FB-04
Triangular wave rising
time coefficient
0.0% to 100.0%
50.0%
✩
FB-05
Set length
0 to 65535 m
1000m
✩
FB-06
Actual length
0 to 65535 m
0m
✩
FB-07
Number of pulses per meter
0.1 to 6553.5
100.0
✩
FB-08
Set count value
1 to 65535
1000
✩
FB-09
Designated count value
1 to 65535
1000
✩
Group FC: Multi-Reference and Simple PLC Function
FC-00
Reference 0
-100.0% to 100.0%
0.0%
✩
FC-01
Reference 1
-100.0% to 100.0%
0.0%
✩
FC-02
Reference 2
-100.0% to 100.0%
0.0%
✩
FC-03
Reference 3
-100.0% to 100.0%
0.0%
✩
FC-04
Reference 4
-100.0% to 100.0%
0.0%
✩
FC-05
Reference 5
-100.0% to 100.0%
0.0%
✩
FC-06
Reference 6
-100.0% to 100.0%
0.0%
✩
FC-07
Reference 7
-100.0% to 100.0%
0.0%
✩
FC-08
Reference 8
-100.0% to 100.0%
0.0%
✩
FC-09
Reference 9
-100.0% to 100.0%
0.0%
✩
FC-10
Reference 10
-100.0% to 100.0%
0.0%
✩
FC-11
Reference 11
-100.0% to 100.0%
0.0%
✩
FC-12
Reference 12
-100.0% to 100.0%
0.0%
✩
FC-13
Reference 13
-100.0% to 100.0%
0.0%
✩
FC-14
Reference 14
-100.0% to 100.0%
0.0%
✩
FC-15
Reference 15
-100.0% to 100.0%
0.0%
✩
FC-16
Simple PLC running mode
0: Stop after running one cycle
1: Keep final values after running one cycle
2: Repeat after running one cycle
0
✩
FC-17
Simple PLC retentive selection
Unit position: Retentive at power down
0: Not retentive
1: Retentive
Tens position: Retentive at stop
0: Not retentive at stop
1: Retentive at stop
00
✩
FC-18
Running time of simple PLC
reference 0
0.0s (h) to 6553.5s (h)
0.0s (h)
✩
FC-19
Acceleration/deceleration time
of simple PLC reference 0
0 to 3
0
✩