6. PANEL OPERATION
Function
Code
Name
Setting Range
Default
Change
Group F9: Fault and Protection (continued)
F9-68
Overspeed detection time
0.0s: Not detected 0.1 to 60.0s
1.0s
✩
F9-69
Detection level of speed error
0.0% to 50.0% (max. frequency)
20.0%
✩
F9-70
Detection time
of speed error
0.0s: Not detected 0.1 to 60.0s
5.0s
✩
F9-71
Power dip ride-through gain Kp
0 to 100
40
✩
F9-72
Power dip ride-through integral
coefficient Ki
0 to 100
30
✩
F9-73
Deceleration time of power dip
ride-through
0 to 300.0s
20.0s
★
Group FA: PID Function
FA-00
PID reference
setting channel
0: Set by FA-01
1: AI1
2: AI2
3: AI3
4: Pulse reference (DI5)
5: Serial comms.
6: Multi-reference
0
✩
FA-01
PID digital setting
0.0% to 100.0%
50.0%
✩
FA-02
PID feedback
setting channel
0: AI1
1: AI2
2: AI3
3: AI1-AI2
4: Pulse reference (DI5)
5: Serial comms.
6: AI1 + AI2
7: Max. (|AI1|, |AI2|)
8: Min. (|AI1|, |AI2|)
0
✩
FA-03
PID operation direction
0: Forward
1: Reverse
0
✩
FA-04
PID reference and
feedback range
0 to 65535
1000
✩
FA-05
Proportional gain Kp1
0.0 to 1000.0
20.0
✩
FA-06
Integral time Ti1
0.01s to 10.00s
2.00s
✩
FA-07
Differential time Td1
0.000s to 10.000s
0.000s
✩
FA-08
PID output limit in
reverse direction
0.00 Hz to maximum frequency
0.00 Hz
★
FA-09
PID error limit
0.0% to 100.0%
0.0%
✩
FA-10
PID differential limit
0.00% to 100.00%
0.10%
✩
FA-11
PID reference change time
0.00 to 650.00s
0.00s
✩
FA-12
PID feedback filter time
0.00 to 60.00s
0.00s
✩
FA-13
PID output filter time
0.00 to 60.00s
0.00s
✩
FA-14
Reserved
—
-
✩
FA-15
Proportional gain Kp2
0.0 to 1000.0
20.0
✩
FA-16
Integral time Ti2
0.01s to 10.00s
2.00s
✩
FA-17
Differential time Td2
0.000s to 10.000s
0.000s
✩
FA-18
PID parameter switchover
condition
0: No switchover
1: Switchover via DI
2: Auto switchover based on PID error
3: Auto switchover based on running
frequency
0
✩
FA-19
PID error 1 for auto switchover
0.0% to FA-20
20.0%
✩
FA-20
PID error 2 for auto switchover
FA-19 to 100.0%
80.0%
✩
FA-21
PID initial value
0.0% to 100.0%
0.0%
✩
FA-22
PID initial value active time
0.00 to 650.00s
0.00s
✩
FA-23
Reserved
—
—
—
FA-24
Reserved
—
—
—