![BENSHAW PowerPro RSI-PPVC-0001-4-3-B-IP20-IM Скачать руководство пользователя страница 71](http://html1.mh-extra.com/html/benshaw/powerpro-rsi-ppvc-0001-4-3-b-ip20-im/powerpro-rsi-ppvc-0001-4-3-b-ip20-im_user-manual_2735254071.webp)
71
6
Function
Code
Name
Setting Range
Default
Change
Group F9: Fault and Protection (continued)
F9-07
Detection of short-circuit to
ground
Units position: Detection of short-circuit
to ground upon power on
0: Disabled
1: Enabled
Tens position: Detection of short-circuit
to ground before running
0: Disabled
1: Enabled
01
✩
F9-08
Braking unit applied voltage
650 to 800 V
760V
★
F9-09
Auto reset times
0 to 20
0
✩
F9-10
Selection of DO action during
auto reset
0: Not act
1: Act
0
✩
F9-11
Delay of auto reset
0.1s to 100.0s
1.0s
✩
F9-12
Input phase loss/
pre-charge relay
protection
Units position: Input phase loss protection
Tens position: Pre-charge relay protection
0: Disabled
1: Enabled
11
✩
F9-13
Output phase loss protection
Units position: Output phase loss protection
0: Disabled
1: Enabled
Tens position: Output phase loss protection
before running
0: Disabled
1: Enabled
01
✩
F9-14
1st fault type
0: No fault
1: Reserved
2: Overcurrent during acceleration
3: Overcurrent during deceleration
4: Overcurrent at constant speed
5: Overvoltage during acceleration
6: Overvoltage during deceleration
7: Overvoltage at constant speed
8: Pre-charge resistor fault
9: Undervoltage
10: AC drive overload
11: Motor overload
12: Power input phase loss
13: Power output phase loss
14: IGBT overheat
15: External fault
16: Communication fault
17: Contactor fault
18: Current detection fault
19: Motor auto-tuning fault
20: Encoder/PG card fault
21: Parameter read and write fault
22: AC drive hardware fault
23: Motor short circuited to ground
24: Reserved
25: Reserved
26: Accumulative running time reached
27: User-defined fault 1
28: User-defined fault 2
29: Accumulative power-on time reached
30: Load lost
31: PID feedback lost during running
40: Fast current limit timeout
41: Motor switchover error during running
42: Too large speed deviation
43: Motor over-speed
45: Motor overheat
51: Initial position error
55: Slave error in master-slave control
—
•
F9-15
2nd fault type
—
•
F9-16
3rd (latest) fault type
—
•