6. PANEL OPERATION
Function
Code
Name
Setting Range
Default
Change
Group A8: Point-point Communication (continued)
A8-03
The slave received data
0: Torque reference
1: Frequency reference
0
✩
A8-04
Zero offset of received
data (torque)
-100.00% to 100.00%
0.00%
★
A8-05
Gain of received
data (torque)
-10.00 to 100.00
1.00
★
A8-06
Point-point communication
interruption detection time
0.0 to 10.0s
1.0s
✩
A8-07
Master data sending cycle in
point-point communication
0.001 to 10.000s
0.001s
✩
A8-11
Window width
0.20 to 10.00 Hz
0.50 Hz
✩
Group AC: AI/AO Correction
AC-00
AI1 measured voltage 1
-10.00V to 10.000V
Factory-
corrected
✩
AC-01
AI1 displayed voltage 1
-10.00V to 10.000V
Factory-
corrected
✩
AC-02
AI1 measured voltage 2
-10.00V to 10.000V
Factory-
corrected
✩
AC-03
AI1 displayed voltage 2
-10.00V to 10.000V
Factory-
corrected
✩
AC-04
AI2 measured voltage 1
-10.00V to 10.000V
Factory-
corrected
✩
AC-05
AI2 displayed voltage 1
-10.00V to 10.000V
Factory-
corrected
✩
AC-06
AI2 measured voltage 2
-10.00V to 10.000V
Factory-
corrected
✩
AC-07
AI2 displayed voltage 2
-10.00V to 10.000V
Factory-
corrected
✩
AC-08
AI3 measured voltage 1
-10.00V to 10.000V
Factory-
corrected
✩
AC-09
AI3 displayed voltage 1
-10.00V to 10.000V
Factory-
corrected
✩
AC-10
AI3 measured voltage 2
-10.00V to 10.000V
Factory-
corrected
✩
AC-11
AI3 displayed voltage 2
-10.00V to 10.000V
Factory-
corrected
✩
AC-12
AO1 target voltage 1
-10.00V to 10.000V
Factory-
corrected
✩
AC-13
AO1 measured voltage 1
-10.00V to 10.000V
Factory-
corrected
✩
AC-14
AO1 target voltage 2
-10.00V to 10.000V
Factory-
corrected
✩
AC-15
AO1 measured voltage 2
-10.00V to 10.000V
Factory-
corrected
✩
AC-16
AO2 target voltage 1
-10.00V to 10.000V
Factory-
corrected
✩
AC-17
AO2 measured voltage 1
-10.00V to 10.000V
Factory-
corrected
✩
AC-18
AO2 target voltage 2
-10.00V to 10.000V
Factory-
corrected
✩
AC-19
AO2 measured voltage 2
-10.00V to 10.000V
Factory-
corrected
✩
The user password protection is used to protect operation on the panel. If this protection has
been enabled, when you finish reading or writing parameters through the keypad and exit, you
need to enter the password to gain access again. Reading and writing are allowed without the
password during communication operation (except FP and FF groups).