4. MECHANICAL INSTALLATION
4.1.3 Installation of RSI-PPVC-00H5-4-3-B-IP20-IM to RSI-PPVC-0200-4-3-X-XN01-IM
1. Backplate Mounting
Drives 0.5 HP – 200 HP support backplate mounting and through-hole mounting.
Follow the guidance below for specific model and application scenarios.
Figure 4-1-3a Backplate mounting of
RSI-PPVC-00H5-4-3-B-IP20-IM to
RSI-PPVC-0050-4-3-B-IP20-IM,
0.5 HP – 50 HP
Figure 4-1-3b Backplate mounting of
RSI-PPVC-0060-4-3-B-XN01-IM to
RSI-PPVC-0200-4-3-X-XN01-IM,
60 HP – 200 HP
CAUTION
• Refer to Figure 4-1-2a and 4-1-2b for
mounting clearance requirements.
Ensure there is sufficient space allowed
for efficient heat dissipation of the drive
and the other devices in the cabinet.
• Mount the AC drive in an upright
position for efficient heat dissipation.
When installing several AC drives
within a cabinet, line up the tops of the
drives. Where an AC drive is required
to be mounted directly above another
AC drive, install an Air Guide Plate, as
shown in Figure 4-1-2d.
• The mounting backplate must be
flame retardant.
• In a location with metallic powders,
mount the AC drive in a fully closed
cabinet with sufficient space. It is
recommended to mount the heat
sink outside the cabinet.
• Mount drive using all mounting holes;
otherwise, the drive may fall off or be
damaged.
Hoisting
holes
Mounting
holes