Product Introduction
Bennett HF H35 Instruction Manual
13
Figure 1.11
–
The
Dräger
Polytron 8200
External Gas Detector
INTERNAL GAS DETECTOR FOR NON-PURGE SYSTEMS (LOCATED INSIDE ELECTRICAL CABINET)
DANGER:
FAILURE TO FOLLOW OEM INSTALLATION INSTRUCTIONS AND MAINTENANCE COULD RESULT IN A FIRE, OR AN
EXPLOSION THAT COULD CAUSE DEATH, PERSONAL INJURY, AND DAMAGE OF PROPERTY.
WARNING: IMPROPER MAINTENANCE CAN CAUSE INJURY OR DAMAGE EQUIPMENT THAT CAN AFFECT BENNETT PACIFIC
SERIES HYDROGEN DISPENSER PERFORMANCE.
CAUTION: Perform all preventative and schedule maintenance checks as recommended by the original manufacturer for all
NON-Bennett components.
IMPORTANT: The
Honeywell Sensepoint XCD RFD Gas Technical Manual
for Use Maintenance and Safety procedures must be
incorporated into the site’s maintenance and safety procedures. Refer to the original manufacturer’s documentation for
specified information. Note: Site documentation should be updated as changes arise (i.e. Regular replacement of sensor).
A non-purged dispenser utilizes a gas detection system that is used to detect flammable gas, toxic gas, and oxygen. Power will be
disconnected from the dispenser and the audio and visual alarm is activated if the level goes over 20%. Please refer to the Honeywell
Sensepoint XCD RFD Technical Manual
located on your dispenser USB for detailed information.
Intended installation area for Dispensers protected by Flammable Gas Detector, including that the area is in an industrial establishment,
has restricted public access, and is governed by conditions of maintenance and supervision that ensure only qualified persons services the
installation.
Figure 1.12
–
Internal Gas Detector
TIMER BOARD FOR PURGED SYSTEMS (LOCATED INSIDE JUNCTION B OX)
A purged dispenser prevents the buildup of explosive atmospheres in the electrical enclosure by using a blower to continuously introduce
air into the enclosure, maintaining a positive pressure differential of at least 0.15 inches of water. If the pressure drops to less than 0.15
inches of water column in the electronic enclosure, the pressure switch shown in
will turn off, causing a timer and relay shown
to remove power from the dispenser until the pressure differential returns to 0.15 inches of water. During the delay, the
volume of air in the cabinet will be circulated at least 4 times and then power will be restored to the dispenser.
Содержание HIGH FLOW H35
Страница 12: ...Product Introduction Bennett HF H35 Instruction Manual 8 DISPENSER IDENTIFICATION NUMBER DIN...
Страница 84: ...Schematics Bennett HF H35 Instruction Manual 80 CHAPTER 8 SCHEMATICS...
Страница 85: ...Schematics Bennett HF H35 Instruction Manual 81...
Страница 86: ...Schematics Bennett HF H35 Instruction Manual 82...
Страница 87: ...Schematics Bennett HF H35 Instruction Manual 83...
Страница 88: ...Schematics Bennett HF H35 Instruction Manual 84...
Страница 89: ...Schematics Bennett HF H35 Instruction Manual 85...
Страница 90: ...Schematics Bennett HF H35 Instruction Manual 86...
Страница 91: ...Schematics Bennett HF H35 Instruction Manual 87...
Страница 92: ...Schematics Bennett HF H35 Instruction Manual 88...
Страница 93: ...Schematics Bennett HF H35 Instruction Manual 89...
Страница 94: ...Schematics Bennett HF H35 Instruction Manual 90...
Страница 95: ...Schematics Bennett HF H35 Instruction Manual 91...
Страница 96: ...Schematics Bennett HF H35 Instruction Manual 92...
Страница 97: ...Schematics Bennett HF H35 Instruction Manual 93...
Страница 98: ...Schematics Bennett HF H35 Instruction Manual 94...