M-4272 Instruction Book
4–46
AUTOMATIC TRANSFER SETTINGS
(ATS)
Path:
System/Setup/Setpoints/Automatic Transfer Settings
The Automatic Transfer Settings selection from the
Transfer Settings group (Figure 4-33) opens the
Automatic Transfer Settings dialog screen (Figure
4-47),
which
includes the following tabs:
•
Setup
•
Fast Transfer
•
Delayed In-Phase Transfer
•
Residual Voltage Transfer
•
Fixed Time Transfer
AUTOMATIC TRANSFER SETTINGS SETUP
TAB
Path:
System/Setup/Setpoints/Automatic Transfer Settings/Setup
Figure 4-47, illustrates the MBTS Automatic Transfer
Settings found under the Setup Tab on the Automatic
Transfer Settings dialog screen.
Automatic Transfer Settings Setup Tab/Auto
Transfer Mode
The Auto Transfer Mode (Figure 4-47) can be Disabled
or Enabled. If Disable is selected and then Save is
selected, then the remaining settings in the Automatic
Transfer Settings dialog screen are grayed out.
HMI Auto Transfer Mode Enable/Disable
To enable or disable Auto Transfer from the Front
Panel perform the following:
1.
Press the
ENTER
pushbutton.
2.
If Level Access is active, the following
is displayed:
ENTER ACCESS CODE
0
a.
Input the required Access Code, then
press
ENTER
.
b.
If the proper Access Code has been
entered, the HMI will return:
LEVEL #(1,2 or 3)
Access Granted!
INIT TRANSFER
INIT
rmte_lcal
c.
Go to Step 4.
3.
If Level Access is not active, then the
following is displayed:
INIT TRANSFER
INIT
rmte_lcal
4.
Press the Right arrow pushbutton until
the following is displayed:
AUTO TRANSFER
AUTO_XFER
man_xfer
5.
Press
ENTER,
the following will be
displayed:
AUTO TRANSFER
disable enable
6.
Press the Left or Right arrow pushbutton
as necessary to enable or disable Auto
Tranfer (upper case).
7.
Press
ENTER
. The following will be
displayed:
AUTO TRANFER
AUTO X_FER
man x_fer
8.
The MBTS is now in the selected Auto
Tranfer Mode. Press
EXIT
as necessary
to return to the Main Menu.
Automatic Transfer Settings Setup Tab/Both S1
& S2 Breakers Open
Both the S1 and S2 Breakers Open portion of the
dialog screen (Figure 4-47) provides a selection for
how the MBTS should respond when both the
Source 1 and Source 2 breakers are open.
In normal operation either the Source 1 or the Source
2 break is closed. If the breaker that is closed is
opened by an external operation when the Block
Transfer is selected, then no transfer is performed
by the M-4272. While this condition continues to
exist any transfer initiated externally or internally will
be blocked and no transfers will occur.
If the Auto Close feature has been selected, then if
the breaker that was closed is opened by an external
operation the other breaker will be closed. The
breaker that is being closed will use the Fast
Transfer, Delayed In-Phase Transfer, Residual
Voltage transfer or Fixed Time Transfer settings of
Содержание M-4272
Страница 1: ...Instruction Book Book 1 of 2 M 4272 Motor Bus Transfer System ...
Страница 45: ...xviii M 4272 Instruction Book This Page Left Intentionally Blank ...
Страница 198: ...System Setup and Setpoints 4 4 87 Figure 4 92 TCM Trip Circuit Monitor Inputs Outputs Selection Dialog Screen ...
Страница 200: ...System Setup and Setpoints 4 4 89 Figure 4 93 ISSLogic Function Dialog Screen ...
Страница 207: ...M 4272 Instruction Book 4 96 This Page Left Intentionally Blank ...
Страница 214: ...Declaration of Conformity Appendix I I 1 IAppendix I Declaration of Conformity ...
Страница 215: ...M 4272 Instruction Book I 2 This Page Left Intentionally Blank ...