M-4272 Digital Motor Bus Transfer System
†
Select the greater of these accuracy values. Accuracy applies to sinusoidal voltage with constant amplitude and
frequency.
TRANSFER SETTINGS
Setpoint
Ranges
Increment
Accuracy
†
Manual Transfer
Fast Transfer
Delta Phase Angle Limit*
0.0 to 90.0 Degrees
0.1 Degree
0.5 Degree
Delta Voltage Limit
0 to 60 V
1 V
0.5 V or
2%
Delta Frequency Limit
0.02 to 2.00 Hz
0.01 Hz
0.01 Hz or
5%
Time Window**
1 to 10 Cycles
0.5 Cycle
1 Cycle
Closing Command
Time Delay***
0 to 10 Cycles
0.5 Cycle
1 Cycle
* Accuracy defined at a constant frequency with a delta frequency of zero (0).
** This timer is used to limit the time window during which a Fast Transfer may be initiated.
*** This time delay is only used for Fast Transfer in Simultaneous mode. The trip and close commands are
normally issued at the same time. This time delay allows the flexibility to delay the closing command to
accomplish the break-before-make mode of operation (open transition).
Delayed In-Phase Transfer
Delta Voltage Limit
0 to 120 V
1 V
0.5 V or
2%
Delta Frequency Limit*
0.10 to 10.00 Hz
0.05 Hz
0.02 Hz (
0.1Hz)***
Time Window**
10 to 600 Cycles
1 Cycle
1 Cycle or
1%
* The pickup accuracy applies to the 60 Hz model at a range of 57 to 63 Hz, and to the 50 Hz model at a
range of 47 to 53 Hz. Beyond these ranges, the accuracy is
0.1 Hz (3-phase);
0.4Hz (single phase).
** This timer is used to limit the time window during which an in-phase transfer may be initiated.
*** Value in parenthese applies to single phase unit.
For Delayed In-Phase Transfer, phase angle accuracy at first phase coincidence is 10.0 degrees with up to
10.0 Hz slip frequency.
Residual Voltage Transfer
Residual Voltage Limit
5 to 60 V
1 V
0.5 V or
2%
Load Shedding Time Delay* 2 to 100 Cycles
1 Cycle
1 Cycle or
1%
* The load shedding command is issued when bus voltage drops below residual voltage limit. The close
command for the Residual Voltage Transfer is sent after the programmed load shedding time delay.
Enabling load shedding option allows the user to assign an output contact to shed load.
Содержание M-4272
Страница 1: ...Instruction Book Book 1 of 2 M 4272 Motor Bus Transfer System ...
Страница 45: ...xviii M 4272 Instruction Book This Page Left Intentionally Blank ...
Страница 198: ...System Setup and Setpoints 4 4 87 Figure 4 92 TCM Trip Circuit Monitor Inputs Outputs Selection Dialog Screen ...
Страница 200: ...System Setup and Setpoints 4 4 89 Figure 4 93 ISSLogic Function Dialog Screen ...
Страница 207: ...M 4272 Instruction Book 4 96 This Page Left Intentionally Blank ...
Страница 214: ...Declaration of Conformity Appendix I I 1 IAppendix I Declaration of Conformity ...
Страница 215: ...M 4272 Instruction Book I 2 This Page Left Intentionally Blank ...