Operation – 2
2–7
•
The delta frequency between the motor
bus and the new source is within the limit
setting. (If this setting is enabled)
•
The Hot Parallel Transfer must be
completed within the time window of 1 to
50 cycles.
Initiate Manual Transfer (ISScom
®
)
To initiate a Manual Transfer of the Motor Bus
utilizing ISScom perform the following:
Q
NOTE
: Communication must be established with
the target MBTS for this procedure.
1.
From the ISScom Main Screen menu bar
select
Monitor
. ISScom will display the
Secondary Metering and Status screen
(Figure 3-17).
2.
Verify that the MBTS is in
Remote
by
observing the Remote Mode/Local Mode
status indicator (System Status).
3.
Verify that the
Transfer Ready (
System
Status) indicator is Green.
4.
If the
Transfer Ready (
System Status)
indicator is not Green, then clear the
condition(s) blocking the transfer.
5.
From the ISScom Main Screen menu
select
Initiate
. ISScom will display the
Initiate Manual Transfer Confirmation
screen (Figure 2-4).
Figure 2-4 Initiate Manual Transfer
Confirmation Screen
6.
Select
YES
, ISScom will display the
Initiate Manual Transfer Command Sent
confirmation screen (Figure 2-5).
Figure 2-5 Initiate Manual Transfer Command
Sent Confirmation Screen
The MBTS will start the Manual Transfer
based on the system parameters present
and MBTS settings.
7.
If the Manual Transfer cannot be
completed the
Incomplete Transfer
Blocked
indicator will be illuminated
(System Status).
The MBTS is blocked from issuing
operation commands.
8.
If the MBTS completes the Manual
Transfer successfully, then the following
will be indicated in the System Status
section of the Secondary Metering and
Status screen:
•
Transfer Completed
•
What type of transfer was completed
•
Close S1(S2) Breaker Command
•
Trip S2(S1) Breaker Command
•
S1(S2) Breaker Closed
•
S2(S1) Breaker Opened
•
Source 1(S2) (New Source)
9.
Select the
RESET
button from the
ISScom comand bar or locally press and
release the
Status Reset
pushbutton to
reset the status indicators.
Initiate Manual Transfer (MBTS Front Panel)
To initiate a Manual Transfer of the Motor Bus from
the MBTS Front Panel perform the following:
1.
Press the
ENTER
pushbutton.
2.
If Level Access is active, the following is
displayed:
ENTER ACCESS CODE
0
a. Input the required Access Code, then
press
ENTER
.
b. If the proper Access Code has been
entered, the HMI will return:
LEVEL #(1,2 or 3)
Access Granted!
INIT TRANSFER
INIT
rmte_lcal
c. Go to Step 4.
Содержание M-4272
Страница 1: ...Instruction Book Book 1 of 2 M 4272 Motor Bus Transfer System ...
Страница 45: ...xviii M 4272 Instruction Book This Page Left Intentionally Blank ...
Страница 198: ...System Setup and Setpoints 4 4 87 Figure 4 92 TCM Trip Circuit Monitor Inputs Outputs Selection Dialog Screen ...
Страница 200: ...System Setup and Setpoints 4 4 89 Figure 4 93 ISSLogic Function Dialog Screen ...
Страница 207: ...M 4272 Instruction Book 4 96 This Page Left Intentionally Blank ...
Страница 214: ...Declaration of Conformity Appendix I I 1 IAppendix I Declaration of Conformity ...
Страница 215: ...M 4272 Instruction Book I 2 This Page Left Intentionally Blank ...